beautypg.com

Delta Electronics VFD-M User Manual

Page 51

background image

Chapter 4 Parameters|

4-16

Revision May 2008, ME14, SW V3.04

Frequency Hold

Applications Purpose

Functions

Related

Parameters

General application

Acceleration/
deceleration pause

Hold output frequency during
Acceleration/deceleration

Pr.39~Pr.42

Auto Restart after Fault

Applications Purpose

Functions

Related

Parameters

Air conditioners,
remote pumps

For continuous and
reliable operation
without operator
intervention

The AC motor drive can be
restarted/reset automatically up to 10
times after a fault occurs.

Pr.72

Pr.113

Emergency Stop by DC Braking

Applications Purpose

Functions

Related

Parameters

High-speed rotors

Emergency stop
without brake
resistor

AC motor drive can use DC braking
for emergency stop when quick stop is
needed without brake resistor. When
used often, take motor cooling into
consideration.

Pr.28
Pr.30
Pr.31

Over-torque Setting

Applications Purpose

Functions

Related

Parameters

Pumps, fans and
extruders

To protect
machines and to
have continuous/
reliable operation

The over-torque detection level can be
set. Once OC stall, OV stall and over-
torque occurs, the output frequency
will be adjusted automatically. It is
suitable for machines like fans and
pumps that require continuous
operation.

Pr.60~Pr.62

Upper/Lower Limit Frequency

Applications Purpose

Functions

Related

Parameters

Pump and fan

Control the motor
speed within
upper/lower limit

When user cannot provide
upper/lower limit, gain or bias from
external signal, it can be set
individually in AC motor drive.

Pr.36
Pr.37