Chapter 4 Parameters|

4-12

Revision May 2008, ME14, SW V3.04

Parameter

Explanation

Settings

Factory

Setting

Customer

Pr.125

Source of PID Set
Point

0.00 to 400.0Hz

0.00

Pr.126

PID Offset Level

1.0 to 50.0 %

10.0

Pr.127

Detection Time of PID
Offset

0.1 to 300.0 sec

5.0

Pr.128

Minimum Reference
Value

0.0 to 10.0 V

0.0

Pr.129

Maximum Reference
Value

0.0 to 10.0 V

10.0

Pr.130

Invert Reference
Signal AVI (0-10V)

00: Not inverted
01: Inverted

00

Pr.131

Minimum Reference
Value (4-20mA)

0.0 to 20.0mA

4.0

Pr.132

Maximum Reference
Value (4-20mA)

0.0 to 20.0mA

20.0

Pr.133

Invert Reference
Signal (4-20mA)

00: Not inverted
01: Inverted

00

Pr.134

Analog Input Delay
Filter for Set Point

00 to 9999 (per 2ms)

50

Pr.135

Analog Input Delay
Filter for Feedback
Signal

00 to 9999 (per 2ms)

5

Pr.136

Sleep Period

0.0 to 6550.0 sec

0.0

Pr.137

Sleep Frequency

0.00 to 400.0 Hz

0.00

Pr.138

Wake Up Frequency 0.00 to 400.0 Hz

0.00

Pr.139

Treatment for Counter
Attained

00: Continue operation
01: Stop Immediately and display E.F.

00

Pr.140

External Up/Down
Selection

00: Fixed Mode (keypad)
01: By Accel or Decel Time
02: Reserved

00

Pr.141

Save Frequency Set
Point

00: Not Save
01: Save

01

Pr.142

Second Source of
Frequency Command

00: Keypad Up/Down
01: AVI (0-10V)
02: ACI (4-20mA)
03: Communication
04: Keypad potentiometer

00

115V/230V: 370-450 Vdc

380.0

460V: 740-900 Vdc

760.0

Pr.143

Software Braking
Level

575V: 925-1075 Vdc

950.0

Pr.144

Total operation time
(Day)

Read Only