Chapter 4 Parameters|

4-84

Revision May 2008, ME14, SW V3.04

Pr. 152

Skip Frequency Width

Settings 0.00 to 400.00Hz

Factory Setting: 0.00

Pr. 153

Bias Frequency Width

Settings

0.00 to 400.00Hz

Factory Setting: 0.00

Frequency

of

Δ top point Fup= master frequency F + Pr.152 + Pr.153.

Frequency of

Δ down point Fdown= master frequency F – Pr.152 – Pr.153.

Fup

Fdown

Pr.10, 12

Pr.11, 13

Pr.152

Master

Frequency
(F)

Double Pr. 153

Pr. 154

Reserved

Pr.155

Compensation Coefficient for Motor Instability

Factory Setting: 0.0

Settings 0.1 to 5.0 (recommended setting 2.0)

0.0

Disable

This parameter is used to improve a condition of unstable current in any specific area. For

higher frequencies, you can adjust this parameter to 0.0, and increase the setting value in

Pr.155 for 30HP and above (a setting of 2.0 is recommended).

Pr.156

Communication Response Delay Time

Settings 0 to 200 (x500µs)

Factory Setting: 0

This parameter is used to set communication response delay time. If you set Pr. 156 to 1 the

communication response delay time will be 1 X 500µs=500µs, set Pr. 156 to 2 the

communication response delay time will be 2 X 500µs=1000µs.

Pr.157

Communication Mode Selection

Factory Setting: 1

Settings

0

Delta

ASCII

1

MODBUS