Chapter 4 Parameters|

Revision May 2008, ME14, SW V3.04

4-7

Parameter

Explanation

Settings

Factory

Setting

Customer

Pr.59

Electronic Thermal
Motor Overload

30 to 300 sec

60

Pr.60

Over-Torque
Detection Mode

00: Over-Torque Detection Disable
01: Enabled during constant speed operation

until the allowable time for detection
(Pr.62) elapses.

02: Enabled during constant speed operation

and halted after detection.

03: Enabled during acceleration until the

allowable time for detection (Pr.62)
elapses.

04: Enabled during acceleration and halted

after detection.

00

Pr.61

Over-Torque
Detection Level

30 to 200 %

150

Pr.62

Over-Torque
Detection Time

0.0 to 10.0 seconds

0.1

Pr.63

Loss of ACI
(4-20mA)

00: Decelerate to 0 Hz
01: Stop immediately and display "EF"
02: Continue operation by last frequency

command

00

Pr.64

User Defined Function
for Display

00: Display AC drive output Frequency (Hz)
01: Display User-defined output Frequency

(H*Pr.65)

02: Output Voltage (E)
03: DC Bus Voltage (u)
04: PV (i)
05: Display the value of internal counter (c)
06: Display the setting frequency (F or o=%)
07: Display the parameter setting (Pr.00)
08: Reserved
09: Output Current (A)
10: Display program operation (0.xxx), Fwd,

or Rev

06

Pr.65 Coefficient K

0.01 to 160.0

1.00

Pr.66

Communication
Frequency

0.00 to 400.0 Hz

0.00

Pr.67

Skip Frequency 1

0.00 to 400.0 Hz

0.00

Pr.68

Skip Frequency 2

0.00 to 400.0 Hz

0.00

Pr.69

Skip Frequency 3

0.00 to 400.0 Hz

0.00

Pr.70

Skip Frequency Band 0.00 to 20.00 Hz

0.00