Component Power-Up and Configuration
03/07/03
8-9
6.
Press F5 or PAGE DOWN to display the next Setup Screen, ANSI Setup.
ANSI Setup
FKey Lock
Off
Send
All
Feature Lock
Off
National
Keypad
Numeric
Send Area
Screen
Cursor Keys
Normal
Print Area
Screen
Xfer Term
EOS
Send Term
None
Char Mode
Multinational
Print Term
None
Char Set
DES-MCS
Print Mode
See Step 7
Keys
Typewriter
Auto Answerback
Off
VT100 ID
VT 100
7.
Set the Print Mode parameter as specified below. Be sure to use the correct parameter
setting for your software version.
●
Set the PRINT MODE parameter to NORMAL and configure the DIRECT PRINTOUT
CHANNEL in SYS_PAR to AUX-0. This parameter combination sends the direct printout
to the Okidata logger and it is not seen on the CRT screen. Any commands done at the
CRT will not be logged unless either output is directed to the logger (using >log with the
command) or if you press CTRL, SHIFT, and PRINT SCREEN simultaneously to toggle
the Main port output to the logger (the message line at the top of the CRT screen will
toggle between FDX MAIN and FDX>AUX when these keys are pressed).
NOTE: If the Okidata printer is connected directly to the Site Controller II, set the Print
Mode parameter to Normal and consult the Site Controller II Installation Manual
for proper connection (RS-232).
●
If you have a Site Controller II
*
below version 1.0F, the PRINT MODE parameter must be
set to AUTO. In AUTO, the Okidata printer will act as a logger and will also print
everything done in command mode. To temporarily suspend output to the printer, press
CTRL, SHIFT, and PRINT SCREEN simultaneously (the message line at the top of the
CRT screen will toggle between FDX>MAIN and FDX>AUX when these keys are
pressed). Press CTRL, SHIFT, and PRINT SCREEN simultaneously to resume output to
the printer.
8.
Press S to save Setup changes.
9.
Press F9 or E to exit Setup Mode.