2 connecting the safety valves, 4burners, 6 configuration examples – Pilz PNOZ m1p base unit User Manual
Page 64
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
4-27
4.6
Configuration examples
4
Burners
4.6.2
Connecting the safety valves
Connecting the safety valves
4-
Funktionsbeschreibung_Steuerung_Sicherheitsventile
If the safety valves are activated via relay outputs, diverse relays must
be used.
The relay output module PNOZ mo5p is intended for that purpose. This
module has 4 relay outputs:
Output O0 is diverse from O1,
Output O2 is diverse from output O3
Connecting the safety valves on a burner in accordance with EN
50156
230 V AC
Interface to pr
evious
module
Interface to next module
O0
O1
13
23
14
24
O2
O3
33
43
34
44