2 connecting the safety valves, 4burners, 6 configuration examples – Pilz PNOZ m1p base unit User Manual

Page 64

background image

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

4-27

4.6

Configuration examples

4

Burners

4.6.2

Connecting the safety valves

Connecting the safety valves

4-

Funktionsbeschreibung_Steuerung_Sicherheitsventile

If the safety valves are activated via relay outputs, diverse relays must

be used.

The relay output module PNOZ mo5p is intended for that purpose. This

module has 4 relay outputs:

Output O0 is diverse from O1,

Output O2 is diverse from output O3

Connecting the safety valves on a burner in accordance with EN

50156

230 V AC

Interface to pr

evious

module

Interface to next module

O0

O1

13

23

14

24

O2

O3

33

43

34

44