Configuration in the PNOZmulti Configurator

3

Safety Mat/Safe Edge

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

3-4

3.4

Configuration in the PNOZmulti Configurator

3400

Configuration in the PNOZmulti Configurator

3-

Schaltmatte_Konfiguration

Operating modes

– Automatic reset (start):

After the pressure-sensitive protective device has been activated,

the output immediately returns to "1" once the pressure-sensitive

protective device is cleared.

– Manual reset (start):

The output does not return to "1" until the reset button has been

pressed. This eliminates the possibility of the reset button being

overridden, triggering automatic activation. A reset is only possible

if the pressure-sensitive protective device is not activated.

Start-up test

The start-up test prevents an automatic restart after a power failure

and subsequent return of voltage. The unit checks whether the non-

activated pressure-sensitive protective device was activated and

cleared after supply voltage was applied.

The output of the pressure-sensitive protective device function ele-

ment is "1" if the pressure-sensitive protective device has not been

activated. This safety function must be retained when this signal is

linked further within the PNOZmulti Configurator:

– Semiconductor outputs: High signal

– Relay outputs: Safety contacts closed

3.4.1

Allocation of test pulses to inputs

Allocation of test pulses to inputs

3-

Schaltmatte_Konfiguration-Zuordnung zu den Eingängen

The test pulses can only be connected to the inputs as follows:

Input 1: Test pulse T0

Input 2: Test pulse T1

or

Input 1: Test pulse T2

Input 2: Test pulse T3

INFORMATION

Test pulses that you use for the pressure-sensitive protective

device cannot be reused for test pulses in conjunction with other

safety devices.