beautypg.com

9 step times, 4burners, 3 configuration in the pnozmulti configurator – Pilz PNOZ m1p base unit User Manual

Page 47

background image

4.3

Configuration in the PNOZmulti Configurator

4

Burners

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

4-10

For the following steps you can select which shutdown type will occur

in the event of an error in the PNOZmulti Configurator:

Safety chain 1 broken (input CHA1)

Safety chain 2 broken (input CHA2)

Ignition and operation safety chain broken (input CHAi)

No air pressure during operation (during start-up: fault lockout)

Faulty flame signal during operation (during start-up: fault lockout)

Please note:

The plant must undergo a hazard analysis to determine whether a safety

shutdown is permitted for an error.

4.3.2.9

Step times

Step times

4-

Funktionsbeschreibung_Ueberwachungen_Schrittzeiten

You can set a time for most of the steps within a cycle (see View burner

cycle, define step times). The time determines how long the step will be

active. While the step is active, the inputs must conform to the pre-de-

fined set values. Once this time has elapsed, the next step will be started

(see also Burner cycle).

When configuring the step times, please note the following with the

steps below:

Steps 5 - 9 "Pre-purge...)

The total duration of steps 5 - 9 for pre-purge must not be less than

the minimum duration for pre-purge calculated via the plant's hazard

analysis.

Step 13 "Ignite ignition flame / 1st safety time"

The configured step time must not be longer than the 1st safety time.

The maximum duration of the 1st safety time is calculated based on

a hazard analysis of the plant.

Step 15 "Ignite ignition flame / 2nd safety time"

The configured step time must not be longer than the 2nd safety

time. The maximum duration of the 2nd safety time is calculated

based on a hazard analysis of the plant.

A step time cannot be set for the following steps: "Burner switched off",

"Check start conditions" and "Burner in operation/control enable".