4.3

Configuration in the PNOZmulti Configurator

4

Burners

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

4-4

4.3.2

Monitoring functions/settings for the burner cycle

Monitoring functions/settings for the burner cycle

4-

4.3.2.1

Combustion air pressure monitoring, activating the combustion air blower, compound con-

troller monitoring

Combustion air pressure monitoring, activating the combustion air blower, compound controller monitoring

4-

Funktionsbeschreibung_Ueberwachungen_Brennertyp

You can set whether the activated burner is a master burner or a slave

burner.

Master burners

Master burners have their own combustion air supply, which is con-

trolled and monitored directly. The following monitoring/control func-

tions are performed on master burners:

– The combustion air pressure is monitored. For this, the "AirP" input

must be linked to the device that monitors the required air amount

(generally an air pressure monitor).

– The combustion air blower is activated via the "BLOW" output.

– The compound controller can be activated and monitored. This is

necessary when an electronic compound controller is present (see

section below, entitled "Compound controller").

Slave burners

Slave burners do not have their own combustion air supply. As a re-

sult, no monitoring takes place. This burner type is used for multi-

burners, for example, which are fitted with a central combustion air

supply and a monitoring function.

Please also note the following with the

Slave burner

type:

The "AirP" input must be connected to a signal indicating the pres-

ence of a central combustion air supply that is functioning correctly.

There is no check to ensure that this input is at rest position when the

burner is switched off.

The burner cannot be started (signal at the "Start" input) until it is

guaranteed that there is no flammable mixture within the combustion

chamber or associated areas or within the exhaust system.

WARNING!

Loss of safety function due to incorrect use of the

Slave bur-

ner

type

If the

Slave burner

type is used to avoid pre-purge and a com-

bustion air supply is not guaranteed, serious injury or death may

result, depending on the application.

Only use the slave burner type if the combustion air supply is

guaranteed elsewhere.