4.5

Inputs and outputs

4

Burners

4.5.2

Element's outputs

Element's outputs

4-

E/As_Ausgänge

SV1: Safety valve 1

Safety valve 1 is activated via this output. Safety valve 1 is on the fuel

side.

SV 1 = 0: Close safety valve 1

SV 1 = 1: Open safety valve 1

If the safety valves are activated via relay outputs, the special re-

quirements of EN 50156 must be considered. We recommend that

the safety valves are activated via the PNOZmulti expansion module

PNOZ mo5p (see section entitled "Examples", under "Connecting

the safety valves").

SV2: Safety valve 2

Safety valve 2 is activated via this output. Safety valve 2 is on the

burner side.

SV 2 = 0: Close safety valve 2

SV 2 = 1: Open safety valve 2

If the safety valves are activated via relay outputs, the special re-

quirements of EN 50156 must be considered. We recommend that

the safety valves are activated via the PNOZmulti expansion module

PNOZ mo5p (see section entitled "Examples", under "Connecting

the safety valves").

IV: Ignition valve

The ignition valve is activated via this output.

IV = 0: Close ignition valve

IV = 1: Open ignition valve

VV: Vent valve

The vent valve is activated via this output. If tightness control is not

configured but continuous vent is, this valve must be designed to be

"normally open". If neither tightness control nor continuous vent is

configured, the output is inactive.

VV = 0: Close vent valve

VV = 1: Open vent valve

IGNT: Ignition transformer

The ignition transformer is activated via this output.

IGNT = 0: Switch off ignition transformer

IGNT = 1: Switch on ignition transformer