beautypg.com

3 flame monitoring, 4 compound controller, 4burners – Pilz PNOZ m1p base unit User Manual

Page 43: 3 configuration in the pnozmulti configurator

background image

4.3

Configuration in the PNOZmulti Configurator

4

Burners

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

4-6

4.3.2.3

Flame monitoring

Flame monitoring

4-

Funktionsbeschreibung_Ueberwachungen_Flammenueberwachung

Flame monitoring is used to establish and signal the presence of a flame.

To ensure that the signal is actually a result of the flame and not of some

external light source, the absence of the flame is monitored during a

burner cycle (e.g. during pre-purge). With direct ignition, the main flame

is monitored.

With indirect ignition you can select between two types of flame moni-

toring:

Joint flame monitoring

Ignition flame and main flame are monitored jointly. The FLAM input

for the main flame must be logically linked to flame monitoring. The

FLAI input for the ignition flame will not then be evaluated.

Separate flame monitoring

Ignition flame and main flame are monitored separately; each have

their own flame monitoring device.

4.3.2.4

Compound controller

Compound controller

4-

Funktionsbeschreibung_Ueberwachungen_Verbundregelung

If master burners have an external electronic compound controller, the

compound controller must be activated and monitored via the burner el-

ement

The compound controller controls and monitors the fuel/air ratio. The

regulating devices for the amount of combustion air and fuel are activat-

ed for this purpose.

The "PURG" output is activated during the step: "Compound control-

ler to pre-purge position". This output signal is intended to switch the

compound controller to the pre-purge position (maximum amount of

combustion air).

During the steps "Pre-purge ...", a signal is expected at the "PUR" in-

put from the compound controller, indicating that the compound con-

troller is in "pre-purge" position. This signal must not occur until the

airflow rate required for pre-purge is present.

The "IGNI" output is activated during the step: "Compound controller

to ignition position". This output signal is intended to switch the com-

pound controller to the ignition position (optimum fuel/air ratio for ig-

nition).

During the steps "Ignition ...", a signal is expected at the "IGN" input

from the compound controller, indicating that the compound control-

ler is in "ignition" position. This signal must not occur until the opti-

mum fuel/air ratio for ignition is present.