4.5

Inputs and outputs

4

Burners

4.5

Inputs and outputs

4500

Inputs and outputs

4-

4.5.1

Element's inputs

Element's inputs

4-

4.5.1.1

Operation

Operation

4-

E/As_Eingänge_Bedienung

Start: Switch burner on

The cycle is started via the start signal. The system can only be start-

ed if no error is present.

Start = 0, no action

Start = 1, switch burner on (pulse edge 0 -> 1)

Stop: Switch burner off

Shutdown of the burner is started via the stop signal.

Stop = 0, no action

Stop = 1, switch off burner

Reset: Fault lockout/reset error

The reset input is used to cancel the restart interlock after a fault

lockout. A reset signal resets the cycle to "Burner switched off" sta-

tus; the burner cycle can be restarted using the start signal.

Reset = 0, no action

Reset = 1, reset (pulse edge 0 -> 1)

4.5.1.2

Monitoring functions

Monitoring functions

4-

E/As_Eingänge_Überwachungen

CHA 1: Safety chain 1

The inputs can be assigned to any signals. We recommend that you

connect E-STOP pushbuttons, which switch off the burner in an

emergency, or plant-dependent monitoring functions, such as tem-

perature or pressure monitoring devices, for example.

CHA 1 = 0: Safety chain interrupted

CHA 1 = 1: Safety chain closed

CHA 2: Safety chain 2

Safety chain 2 has the same function as safety chain 1. Both safety

chains are of equal value. They are differentiated to improve diagnos-

tics.

CHA 2 = 0: Safety chain interrupted

CHA 2 = 1: Safety chain closed

CHAi: Ignition and operation safety chain

This input has the same function as safety chains 1 and 2. However,

when there is a 0 signal, a fault lockout or safety shutdown will only

occur in between the steps Pre-ignition and Burner in operation, in-

clusive. If the input has a 0 signal before or after this point, it will have

no effect.

CHAi = 0: Safety chain interrupted

CHAi = 1: Safety chain closed