Configuration in the PNOZmulti Configurator

2

Muting

2.3.3

Output parameters

Output parameters

2-

Muting_Konfiguration_Ausgangsparameter

Enable

Enable = 0: Error detected (e.g. simultaneity exceeded)

Enable = 1: The enable is granted if no error has been detected.

Muting active

Display of muting status (e.g. for activating a lamp)

Muting active = 0: No muting (light curtain not suspended)

Muting active = 1: Muting active (light curtain suspended)

2.3.4

Monitoring times

Monitoring times

2-

Muting_Konfiguration_Überwachungszeiten

Maximum muting time

This setting is used to adjust the maximum permitted muting time.

Permitted value range: 1 ... 900s (= 15 minutes)

Simultaneity

This setting is used to define the maximum time (synchronisation

time) which is permitted to elapse between the actuation (0/1-pulse

edge) of muting sensors 1 and 2 or muting sensors 3 and 4.

Permissible value range for parallel muting and cross muting: 1 ... 3 s

Permitted value range for sequential muting: 1 ... 30 s

Bounce time

This setting can be used to set the time up to the point at which the

muting sensors finally make contact.

Permitted value range: 50 ..0.800 ms

2.3.5

Suspension of muting (override)

Suspension of muting (override)

2-

Muting_Konfiguration_Muting-Überbrückung_Override

If there are faults, the muting station can be overridden via the muting

override input parameter.

Start-up condition

Muting override can be switched on if at least one of the muting sen-

sors is active. The enable output and

muting active

output parameter

are set during the override. The override is monitored and has a max-

imum duration that corresponds to the set muting time.

Switch-off condition

Muting override is switched off if

– the muting time has elapsed

or

– no muting sensor is active and the light curtain is clear

or

– muting override is reset to 0 (release override button).