Configuration examples, 1 burner configuration, 1 burner structure – Pilz PNOZ m1p base unit User Manual
Page 62: 2 burner properties, 4burners, 6 configuration examples
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
4-25
4.6
Configuration examples
4
Burners
4.6
Configuration examples
4600
Configuration examples
4-
4.6.1
Burner configuration
Burner configuration
4-
4.6.1.1
Burner structure
Burner structure
4-
Brenneraufbau
4.6.1.2
Burner properties
Burner properties
4-
Brennereigenschaften
The burner has the following properties:
The burner has its own combustion air supply.
An electronic compound controller is present
A separate ignition burner is present
The ignition flame is extinguished once the main burner is successful-
ly ignited.
Ignition and main flame are each monitored using their own flame
monitoring device.
A tightness control check is carried out prior to ignition (during pre-
purge).
With tightness control, the section between the two safety valves is
vented via the vent valve.
Safety valve 2 is closed during afterburn.
Safety valve 1
Safety valve 2
Vent valve
Ignition valve
Separate
flame monitoring