Configuration examples, 1 burner configuration, 1 burner structure – Pilz PNOZ m1p base unit User Manual

Page 62: 2 burner properties, 4burners, 6 configuration examples

background image

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

4-25

4.6

Configuration examples

4

Burners

4.6

Configuration examples

4600

Configuration examples

4-

4.6.1

Burner configuration

Burner configuration

4-

4.6.1.1

Burner structure

Burner structure

4-

Brenneraufbau

4.6.1.2

Burner properties

Burner properties

4-

Brennereigenschaften

The burner has the following properties:

The burner has its own combustion air supply.

An electronic compound controller is present

A separate ignition burner is present

The ignition flame is extinguished once the main burner is successful-

ly ignited.

Ignition and main flame are each monitored using their own flame

monitoring device.

A tightness control check is carried out prior to ignition (during pre-

purge).

With tightness control, the section between the two safety valves is

vented via the vent valve.

Safety valve 2 is closed during afterburn.

Safety valve 1

Safety valve 2

Vent valve

Ignition valve

Separate

flame monitoring