beautypg.com

4burners, 5 inputs and outputs – Pilz PNOZ m1p base unit User Manual

Page 59

background image

4.5

Inputs and outputs

4

Burners

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

4-22

AirP: Combustion air pressure monitoring

The combustion air pressure is monitored at this input.

AirP = 0: Combustion air pressure absent

AirP = 1: Combustion air pressure present

On slave burners it is assumed that the furnace is fitted with a central

combustion air supply. In this case, the "AirP" input must be con-

nected to a signal indicating the presence of a correctly functioning

combustion air supply.

FLAM: Flame monitoring of main flame

The main flame is monitored at this input. If a burner type with joint

flame monitoring is configured, this input will also be used to monitor

the ignition flame.

FLAM = 0: Flame absent

FLAM = 1: Flame present

FLAI: Flame monitoring for ignition flame

If a burner type with separate flame monitoring is configured, this in-

put will be used to monitor the ignition flame.

FLAI = 0: Ignition flame absent

FLAI = 1: Ignition flame present

PUR: Compound controller in pre-purge position

At this input, a signal is expected from the compound controller, in-

dicating that the compound controller is in "pre-purge" position. This

signal must not come from the compound controller until the airflow

rate required for pre-purge is present.

PUR = 0: Compound controller not in pre-purge position

PUR = 1: Compound controller in pre-purge position

IGN: Compound controller in ignition position

At this input, a signal is expected from the compound controller, in-

dicating that the compound controller is in "ignition" position. This

signal must not occur until the optimum fuel/air ratio for ignition is

present.

IGN = 0: Compound controller not in ignition position

IGN = 1: Compound controller in ignition position

GP: Tightness control (gas pressure)

The pressure between the two safety valves is monitored at this in-

put.

GP = 0: Section vented (atmospheric pressure)

GP = 1: Gas pressure present

HTmp: High temperature mode

This input is used to switch between "Normal mode" and "High tem-

perature mode". It is only possible to switch to high temperature

mode if

Allow "High temperature" mode

has been selected in the

PNOZmulti Configurator.

HTmp = 0: Normal operation

HTmp = 1: High temperature