4.4.2

Errors during the burner cycle

Errors during the burner cycle

4-

Funktionsbeschreibung_Schritte_Verhalten_im_Fehlerfall

An error is detected if the input signals within a step fail to match the val-

ues set for the monitoring operation. This will lead either to a fault lock-

out or a safety shutdown, depending on the input signal and

configuration. Some of the monitoring functions during a burner cycle

depend on the step, while others are continuous. In other words, some

monitoring processes occur in a specific step, while others may be ac-

tive across the whole cycle.

Step-dependent errors

With step-dependent errors, the set value of the input signals in the

various steps may vary.

E.g.: With combustion air monitoring, the input must have a "0" signal

during the "Check start conditions" step and a "1" signal during the

"Burner in operation" step.

The following monitoring functions have errors that depend on the

specific step:

– Combustion air monitoring

– Flame monitoring of ignition flame

– Flame monitoring of main flame

– Tightness control

– Compound controller not in pre-purge position

– Compound controller not in ignition position

– Ignition and operation safety chain

Step-independent errors

Where errors are independent of the specific step, the same set value

applies for each step: The input must have a "1" signal.

The following monitoring functions have errors that are independent

of the specific step:

– Safety chain 1

– Safety chain 2