3 sequence errors, 2muting, 4 operating modes – Pilz PNOZ m1p base unit User Manual
Page 18
2.4
Operating modes
2
Muting
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
2-10
2.4.2.3
Sequence errors
Sequence errors
2-
Muting_Betriebsarten_sequenzielles Muting-Sequenzfehler
The muting sensors must be operated in a specific sequence in sequen-
tial mode. Once a particular directional movement has started (entry or
exit), it must be fully completed. Any deviation from the sequence shown
causes the enable output (enable = 0) and the output parameter
Muting
active
to reset.
Vehicle length W greater than distance C between MS1 and MS4
All sensors are temporarily operated as the vehicle passes through. The
first muting sensor (MS1 upon entering, MS4 upon exiting) only be-
comes clear once all muting sensors have been operated.
MS1
MS2
MS3 MS4
AOPD
W > C
A
B
C