Inputs and outputs
4
Burners
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
4-24
BLOW: Combustion air blower
The combustion air blower is activated via this output.
BLOW = 0: Switch off combustion air blower
BLOW = 1: Switch on combustion air blower
PURG: Compound controller to pre-purge position
This output is used to signal to the compound controller to go to pre-
purge position.
PURG = 0: Compound controller not activated
PURG = 1: Compound controller to pre-purge position
IGNI: Compound controller to ignition position
This output is used to signal to the compound controller to go to ig-
nition position.
IGNI = 0: Compound controller not activated
IGNI = 1: Compound controller to pre-purge position
STRT: Compound controller: Start position
This output is used to signal to the compound controller to go to start
position.
STRT = 0: Compound controller not activated
STRT = 1: Compound controller to start position
CONT: Control enable
This output provides the signal for the control enable.
CONT = 0: No control enable
CONT = 1: Control enable