3 configuration in the pnozmulti configurator, 4burners, 6 configuration examples – Pilz PNOZ m1p base unit User Manual
Page 63
4.6
Configuration examples
4
Burners
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
4-26
4.6.1.3
Configuration in the PNOZmulti Configurator
Configuration in the PNOZmulti Configurator
4-
Konfiguration im PNOZmulti Configurator
Select burner type
Select
Master burner, indirect ignition, separate flame monitoring
Configure compound controller monitoring
Configure combustion air pressure monitoring
Configure ignition
Configure tightness control
Configure settings for shutting down the burner
Burner properties
Configuration
Own combustion air supply
Master burner
Separate ignition burner
Indirect ignition
Separate monitoring of ignition and main
flame
Separate flame monitoring
Burner properties
Configuration
Electronic compound controller present
Cycle with compound control-
ler
Burner properties
Configuration
A bounce time must be stated for shutting
down the combustion air blower
Debounce time:
300 ms
Burner properties
Configuration
Ignition flame is extinguished once the
main burner is ignited
Ignition valve
Closed after ignition
Burner properties
Configuration
Vent via vent valve
Type of tightness control
Vent via vent valve
Tightness control occurs prior to ignition
Time of tightness control
Prior to ignition
Burner properties
Configuration
Safety valve 2 is closed during afterburn.
Safety valve 2 is closed during
afterburn