background image

4.6

Configuration examples

4

Burners

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

4-26

4.6.1.3

Configuration in the PNOZmulti Configurator

Configuration in the PNOZmulti Configurator

4-

Konfiguration im PNOZmulti Configurator

Select burner type

Select

Master burner, indirect ignition, separate flame monitoring

Configure compound controller monitoring

Configure combustion air pressure monitoring

Configure ignition

Configure tightness control

Configure settings for shutting down the burner

Burner properties

Configuration

Own combustion air supply

Master burner

Separate ignition burner

Indirect ignition

Separate monitoring of ignition and main
flame

Separate flame monitoring

Burner properties

Configuration

Electronic compound controller present

Cycle with compound control-
ler

Burner properties

Configuration

A bounce time must be stated for shutting
down the combustion air blower

Debounce time:

300 ms

Burner properties

Configuration

Ignition flame is extinguished once the
main burner is ignited

Ignition valve

Closed after ignition

Burner properties

Configuration

Vent via vent valve

Type of tightness control

Vent via vent valve

Tightness control occurs prior to ignition

Time of tightness control

Prior to ignition

Burner properties

Configuration

Safety valve 2 is closed during afterburn.

Safety valve 2 is closed during
afterburn