Appendix, Startup form – Reznor RXH (Outdoor PreevA) Unit Installation Manual User Manual
Page 64
Form I-RDH/REH/RHH/RXH (12-14), Page 64
APPENDIX
Job Name:
Contractor Contact:
Street Address
Contractor Phone:
City, State, Zip
Model #
Date:
Serial #
Contractor:
Tag:
General Checks
Reference
NOTE: Checks may not apply depending on option selection.
□ Inspect unit for damage.
Paragraph 3.0
□ Verify shipping brackets are removed.
□ Check fuses/breakers for correct sizing. (Check rating plate for electrical requirements.)
□ Check clearances.
Paragraph 4.1
□ Check all condensate connections. Fill all traps.
Paragraph. 6.2 &
Paragraph 6.6
□ Verify air filters are installed.
□ Inspect dampers.
□ Tighten all screws on pulleys and fans.
Paragraph 6.9
□ Check and tighten all electrical terminals.
□ Seal electrical entrances.
□ Check optional dirty filter switch.
Paragraph 7.6.3
□ Check for manual resets (firestat, high gas pressure switch).
□ Verify all copper tubing is isolated and does not rub.
□ Verify crankcase heater energized 24 hrs before startup.
Blower Assembly
□
Fan alignment Motor HP: ________ Name Plate Amps: ______
□
Belt tension
Motor Make/Amps: L1 L2 L3
______________ ______ ______ ______
□
VAV controls
Reheat Compressor Data
Outdoor Air Conditions:
Dry Bulb: _______________
Wet Bulb: ____________
Circuit
L1
L2
L3
Name Plate RLA Head Pressure PSIG
Suction Pressure PSIG
Reheat
Gas Heating Section
□
LP
□
Natural Gas
□
Leak test gas piping
□
Purge air from lines
□
Check Inlet Gas
Pressure
Maximum: 14” w.c. for both
natural gas and LP
Actual Gas Inlet
Pressure: _________
Minimum: As listed on the
unit rating plate
□
Check Manifold Pressure (As listed on the rating plate.)
Actual Manifold Gas Pressure:____________
Electric Heating Section
Heater Number and Amps:
1
2
3
4
5
6
Start-Up Checklist
NOTE: See
Paragraph 9.0 for
complete list.
STARTUP FORM
Fill out the applicable sections and keep for future reference.