beautypg.com

3 startup warnings and checklist – Reznor RXH (Outdoor PreevA) Unit Installation Manual User Manual

Page 61

background image

Form I-RDH/REH/RHH/RXH (12-14), P/N 215210 R14, Page 61

Check heat operation.

WARNINGS

For your safety, read before operating. If you do not follow these instructions exactly, a fire

or explosion may result causing property damage, personal injury, or death.

• RDH and RHH - These appliances do not have a pilot. They are equipped with an ignition

device which automatically lights the burner. Do not try to light the burner manually

• Before operating, smell all around the appliance area for gas. Be sure to smell next to the floor

because some gas is heavier than air and will settle on the floor.

WHAT TO DO IF YOU SMELL GAS

• Do not try to light any appliance.

• Do not touch any electrical switch; do not use any phone in your building.

• Leave your building immediately.

• Immediately call your gas supplier from a phone remote from the building. Follow the gas

supplier’s instructions.

• If you cannot reach your gas supplier, call your fire department.

9.3 Startup Warnings

and Checklist

CAUTION: If equipped with a cooling module with reheat, the

crankcase heater must be allowed to warm up for at least 24 hours

prior to startup. Disable cooling controls before turning on power

to warmup crankcase heaters. See Hazard Levels, page 2.

Close and latch the doors.

IMPORTANT: If equipped with digital controls, when turning on the main controller

for the first time, be sure to push and hold the Function Key for five seconds. This

should cause the first LED to light. If the LED light is lit, the controller will remain on

and allow for remote control even after a power outage. If the LED light is not lit, it

will be necessary on restart the controller at the unit after a power outage.

Read and follow the preparation instructions below on power supply voltage

phasing. When ready, turn on the power. Turn on the gas.

Power Supply Voltage Phasing

Because it is possible to unknowingly connect 3-phase power in such a way as

to cause the blower and, if there is an optional reheat compressor, the scroll

compressor to rotate in reverse, it is very important to check this on startup.
Blower Rotation - Check rotation on startup. If blower rotation is not correct, reverse

by interchanging two wires on the 3-phase supply connection to the blower motor.
Check Reheat Compressor (if equipped) - Connect refrigerant pressure gauges to

the suction and discharge lines of the compressor and an electric meter to the power

supply.

CAUTION: Be sure to connect pressure gauges to the suction

and discharge lines before system startup so that compressor

rotation can be checked immediately. A scroll compressor will

be destroyed if allowed to operate in the wrong direction. See

Hazard Levels, page 2.

Adjust the controller so that a call for reheat exists. Immediately at startup,

observe the gauges. If the suction pressure rises and discharge pressure

drops, the compressor is operating in reverse and must be shut down. Turn

off the power and switch the 3-phase line voltage wiring connections before

restarting the unit.

(Important NOTE: If allowed to operate for several minutes in reverse, the compres-

sor’s internal protector will trip. If a compressor is repeatedly allowed to restart and

run in reverse, the compressor will be permanently damaged.)

9.2.4 Cooling (if

equipped) Checklist

Prior to Startup:

Verify that the condensate drain(s) are connected and properly trapped.

(Paragraphs 6.2 and 6.6.4)

Verify that the refrigerant circuits are charged with the appropriate refrigerant and

leak tested according to the condensing unit instructions.