Form I-RDH/REH/RHH/RXH (12-14), Page 28

Depending on the control option ordered (identified on the wiring diagram), the mix-

ing box may or may not have dampers. Depending on the configuration and controls,

dampers may be outside air only or outside and return air with manual or motorized

control. Damper motor may be 2-position, 3-position, or modulating and may be con-

trolled by unit operation, unit operation and a damper position dial (potentiometer),

discharge temperature, mixed inlet air temperature, building pressure, or a building

automation system.

Motorized dampers always close on shutdown.

TABLE 19 - Air Inlet and

Damper Controls by

Mixing Box Option

Mixing Box

Configuration

(see FIGURE 20)

Air Inlet Control

Option (Check

wiring diagram.)

Opening and

Dampers

Damper Motor Function

(damper position)

Dampers Controlled by

Option GD6

GE1

30% Outside and

100% Return Air

30% outside air maximum;

100% return air (no damper) Manual damper

GE2

2-position (open/closed) 30%

outside air damper; 100%

return air (no damper)

System control (switch or field-supplied time clock).

Option GD1 or

GD2

GE3

100% Outside Air

Opening only with

Dampers

2-position (open or closed)

Unit operation.

GE4

3-position (2 open positions or

closed)

Unit operation with damper "stop" set by unit-mounted adjustable

damper dial (potentiometer).

Option GD4

NONE

100% Outside Air and Return Air Openings but no factory-installed dampers or controls.

GE5

100% Outside and

100% Return Air

Openings, both with

Dampers

None

Damper controlled by a manual quadrant.

GE6

2-position (outside air open or

return air open)

System control (switch or field-supplied time clock).

*GE7

Return air temperature provides warm-up or cool-down by delaying

opening of outside air damper.

GE8

3-position (2 mixed positions or

return air only)

Unit operation with damper "stop" set by unit-mounted adjustable

damper dial (potentiometer).

GE10

Modulates outside air and

return air dampers to provide

mixture of outside and return

air in response to control

Unit operation with damper “stop” set from a remote adjustable

damper dial (potentiometer). Requires installation of shipped-separate

potentiometer; follow manufacturer’s instructions.

GE11

Discharge air temperature.

GE12

Discharge air temperature with unit-mounted adjustable damper dial

(potentiometer) set to always provide a minimum amount of outside

air.

*GE13

Discharge air temperature plus return air temperature setting to

provide warm-up or cool-down by delaying opening of outside air

damper.

*GE14

Discharge air temperature plus return air temperature providing

warm-up or cool-down by delaying opening of outside air damper

and with unit-mounted adjustable damper dial (potentiometer) set to

always provide a minimum amount of outside air after delay.

GE15

Building pressure. Requires installation of shipped-separate pressure

null switch. See page 29 and follow manufacturer's instructions.

GE16

DDC control from field-supplied automated building system

GE21

Applies to PREEVA

®

systems with optional cooling operation; outside

air damper is controlled by enthalpy (heat content in a lb of air) using

an economizer logic module. On a call for low stage cooling if the

enthalpy of outdoor air becomes low, the outdoor air damper opens

to reduce the cooling load in the building. As enthalpy of outdoor

air increases, the outdoor air damper closes to a preset minimum

condition. During economizer operation, the mechanical cooling is

operated by stage 2 cooling on the space thermostat. The economizer

is automatically locked out during heating and holds the outdoor air

damper at the minimum position setting. Enthalpy sensor is shipped

separately for field installation in the outside air inlet. See instructions

beginning on page 29.

GE22

Applies to PREEVA

®

systems with optional cooling. In cooling mode,

both outside air and return air dampers are modulated by enthalpy

(heat content in a lb of air) using an economizer logic module. On a

call for low cooling if the outdoor air enthalpy is lower than the return

air enthalpy, the outdoor air damper proportions open. If the outdoor

air enthalpy is higher than the return air enthalpy, the outdoor air

damper closes to minimum position. If outdoor air enthalpy and return

air enthalpy are equal, the outdoor air damper proportions open.

During economizer operation, the mechanical cooling is operated

by stage 2 cooling on the space thermostat. The economizer is

automatically locked out during heating and holds the outdoor air

damper at the minimum position setting. Enthalpy sensors are shipped

separately for field installation in the return air duct and the outside air

inlet. See instructions beginning on page 29.

*GE7 provides ASHRAE Cycle I; GE14 provides ASHRAE Cycle II; GE13 provides ASHRAE Cycle III

6.0 Mechanical

(cont’d)

6.4.5.3 Mixing Box Damper and Control Options

6.4 Unit Inlet Air