beautypg.com

Reznor RXH (Outdoor PreevA) Unit Installation Manual User Manual

Page 29

background image

Form I-RDH/REH/RHH/RXH (12-14), P/N 215210 R14, Page 29

The pressure null switch used in Option GE15 is a Dwyer #1640-0 with a range of .01-

.20” w.c. It is shipped separately for field installation. Refer to the following paragraphs

and the manufacturer’s installation instructions included with the switch.
Description and Application - The pressure null switch is a diaphragm operated dif-

ferential pressure switch used in makeup air applications to control building pressure.

It maintains a selected positive or negative pressure setpoint by changing the amount

of outside air being introduced to the building through the modulating outside air damp-

ers. As more pressure is required in the building, the pressure null switch activates the

damper motor driving the outside air damper towards the full open position and the

recirculated air damper towards the closed position. Conversely, as less pressure is

required, the switch drives the dampers in the opposite direction.

Pressure Null Switch

(Field installed to

control Outside Air

Dampers in Option

GE15)

Pressure Null Switch

Installation Instructions

1. Select an indoor location free from excessive vibration

where oil or water will not drip onto the switch and where

ambient temperature will be within a range of -30°F (dry

air) to 110°F.

2. Mount the switch securely with the diaphragm in a

vertical plane to ensure proper operation.

3. Connect the pressure taps on the top of the switch to

sources of air pressure differential. Metal tubing with

1/4” O.D. is recommended, but any tubing system

which will not unduly restrict the air flow may be used.

To maintain a positive building pressure, vent the

low pressure tap to the outdoors and allow the high

pressure tap to monitor building pressure. To maintain

a negative building pressure, reverse the functions of

the high and low pressure taps. In either case, be sure

that the outdoor vent is protected from the wind and

screened from insects.

4. Adjustment of the Switch - The “HIGH” actuation point

of the null switch is indicated on a calibrated scale

secured to the transparent range screw enclosure.

Building pressure is set by turning the adjustment

screw. The “Low” actuation point is set by adjusting the

span of the null by turning the span adjustment screw.

The span range is .01 to .03” w.c.

5. See the wiring diagram included with the furnace to

make electrical connections.

IMPORTANT: To eliminate shipping damage

to the switch contacts, the manufacturer

reduced the span adjustment to zero before

shipping. The span should be adjusted

prior to using the switch. (If the switch has

been installed, disconnect the vent tube so

that the null switch is in a neutral position.)

Remove the electrical box cover and while

observing the contacts, turn the span

adjustment screw slowly in a clockwise

direction. Continue turning the adjustment

screw until you are able to see gaps

between the common and both the low and

high contacts. A minimum gap provides the

greatest sensitivity. The wider the gap the

lower the sensitivity.

Electric

Box

Span

Adjust

Screw

Mounting Plate

Pressure

Taps

Low

High

Pressure

Adjust Screw

Increasing

Decreasing

Linkage to

Diaphragm

Low

Common

High

Span Adjustment

Span of

floating

contact

Switching action in the pressure

null switch

FIGURE 23 - Pressure Null Switch

(used with Inlet Air Option GE15)

Pressure Null

Switch, P/N 88052

Enthalpy Sensor(s)

- Field installed to

control dampers in

economizer Options

GE21 and GE22)

Option GE21 requires installation of one sensor; Option GE22 requires installation of

two sensors. A system with Option GE21 includes one field-installed parts bag. A sys-

tem with Option GE22 includes two field-installed parts bags. Locate the parts bag(s)

shipped inside the unit. Check components against the list below.

TABLE 20 -

Components in each

Enthalpy Sensor

Parts Bag, P/N 220686

(Option GE21 requires

one parts bag; Option

GE22 requires two.)

Qty Component Description

P/N

1 Enthalpy Sensor, Honeywell #C7400A1004

196290

1 Blue Wire Assy, 18 ga x 72” with terminals

220621

1 Purple Wire Assy, 18 ga x 72” with terminals

220620

2 Screws, #6 x 3/4” long

110650

2 5/8” Strain Relief, Heyco #SR6N-4

100392

4 Stick-on Wire Retainers, Cable Fast-Fastex

#8511-29-00

142678

2 Plastic Wire Ties

20913