Reznor RXH (Outdoor PreevA) Unit Installation Manual User Manual

Page 39

background image

Form I-RDH/REH/RHH/RXH (12-14), P/N 215210 R14, Page 39

Horizontal Discharge Duct Flange for Model RXH with a hot water heat module

(For Model RXH without a hot water heat module, see Paragraph 6.8.2.) - Optional

duct flange is factory installed. See dimensions for connecting ductwork in

FIGURE

36B. See duct connection requirements in Paragraph 6.8.4.

Airflow

A

B

C

D

E

Outlet

Opening

19 (483)

3-1/2 (89)

2-5/16

(59)

7-7/32

(183)

1 (25)

20-5/32 (512)

22-1/2 (572)

7-23/32

(196)

Water

Inlet

Water

Outlet

8-7/8

(225)

Option AX4

Duct Flange

(See FIGURE
36B.

)

Side View

Front View

FIGURE 36A - Dimensions

of Hot Water Heat Module,

Option HW2 - inches (mm)

TABLE 25A - Dimensions

RXH

000A 000B 000C 000D 000E

A

inches

4-27/32

4-1/8

mm

123

105

B

inches

6-5/8

6-7/8

mm

168

175

C

inches

24

34

24

40

48

mm

610

864

610 1016 1219

D

inches

24

34

mm

610

864

E

inches

9-9/16 8-27/32

8-3/8

mm

243

225

213

• Type of Ductwork - The type of duct installation to be used depends in part on the

type of construction of the roof (whether wood joist, steelbar joist, steel truss, pre-cast

concrete) and the ceiling (whether hung, flush, etc.).

• Ductwork Material - Rectangular duct should be constructed of not lighter than No.

26 U.S. gauge galvanized iron or No. 24 B & S gauge aluminum.

• Ductwork Structure - All duct sections 24 inches (610mm) or wider, and over 48

inches (1219mm) in length, should be cross broken on top and bottom and should

have standing seams or angle-iron braces. Joints should be S and drive strip, or

locked.

Through Masonry Walls - No warm air duct should come in contact with masonry

walls. Insulate around all air ducts through masonry walls with not less than 1/2” (1”

is recommended) of insulation.

Through Unheated Space - Insulate all exposed warm air ducts passing through

an unheated space with at least 1/2” (1” is recommended) of insulation.

• Duct Supports - Suspend all ducts securely from adjacent buildings members. Do

not support ducts from unit duct connections.

• Duct Sizing - Proper sizing of the supply air ductwork is necessary to ensure a sat-

isfactory heating installation. The recognized authority for such information is the Air

6.8.4 Requirements

and Recommendations

for Connecting and

Installing Ductwork

TABLE 25B - Dimensions of Discharge Duct

Flange on Model RXH with an Optional Hot

Water Heat Module

RXH with Option HW2

H

W

000A

inches

23-3/4

23-15/16

mm

603

608

000B

inches

23-3/4

33-15/16

mm

603

862

000C

inches

33-3/4

23-15/16

mm

857

608

000D

inches

33-3/4

39-15/16

mm

857

1014

000E

inches

33-3/4

47-15/16

mm

857

1218

FIGURE 36B - Option

AX4, Discharge Duct

Flange on Model RXH

with Optional Hot Water

Heat Module

Hot Water

Module,

Option HW2,

with factory-

installed

Duct Flange,

Option AX4