beautypg.com

0 controls and operation, 1 gas valve - model rdh and model rhh, 0 electrical (cont’d) – Reznor RXH (Outdoor PreevA) Unit Installation Manual User Manual

Page 50

background image

Form I-RDH/REH/RHH/RXH (12-14), Page 50

Option BD4 (factory-installed) or Option BD5 (field-installed) 200°F fir-

estat is

P/N 42782. Firestat Option BD4 is factory installed in the mixing

box to sense the temperature of the return air. Firestat Option BD5 is

shipped separately for field installation in the discharge ductwork.
The firestat will shutdown the unit if temperature setpoint is reached.

Comply with local building codes.

7.6.4 Firestat, Option

BD4 or BD5 - RDH,

REH. RHH, RXH

Limit control,

P/N 211480, is factory installed to monitor the tempera-

ture of the discharge air. Setpoint of automatic reset control is adjust-

able. (

NOTE: Not needed with digital controls; standard function of

the digital controller.)

7.6.5 Discharge

Temperature Low Limit

(Freezestat), Option

BE2 - RDH, REH, RHH,

RXH

7.6.6 High Ambient

Limit Control (burner

cutoff), Option BN2 -

RDH, REH, RHH, RXH

The high ambient limit control monitors the temperature of

the outside air and activates to shutoff the burner if the set-

point is reached. The control has an adjustable setpoint and

resets automatically.

P/N is 126170.

A DPDT plug-in relay is installed for coordination of unit opera-

tion with the operation of the building exhaust fan. Plug-in relay

P/N is 211411; socket P/N is 211415.

7.6.7 Exhaust Fan Interlock

Relay, Option BG9 - RDH,

REH, RHH, RXH

7.0 Electrical (cont’d)

7.6 Other Optional Electrical Components (cont’d)

This photoelectric smoke detector is shipped separately to

be installed in the discharge ductwork. Follow installation

instructions supplied with the control and the wiring on the

unit wiring diagram. Comply with local building codes. P/N

of the device is

159553.

7.6.8 Smoke Detector,

Option SA1 - RDH,

REH, RHH, RXH

8.0 Controls and

Operation

Gas-fired furnaces are equipped with a 24-volt combination valve which includes the

automatic electric on-off valve the pressure regulator, the safety pilot valve, and the

manual shutoff valve. Valve on/off function is controlled by the room thermostat or

digital controller.

8.1 Gas Valve - Model RDH and Model RHH

WARNING

The operating valve is the prime safety shutoff. All gas supply lines

must be free of dirt or scale before connecting the unit to ensure

positive closure. See Hazard Levels, page 2.

8.2.1 Single-Stage Operation - Recirculated Heating Only (Option AG1

applies to Model RDH and Model RHH; Option EG1 applies to Model REH)

The single-stage gas valve on Models RDH and RHH allows for single-stage control

from a single-stage, 24-volt thermostat. On Model REH, the heating elements are con-

trolled by a single-stage, 24-volt thermostat.
The thermostat can either be selected as an option or be field supplied. Follow the

thermostat manufacturer’s instructions for installation. Make wire connections accord-

ing to the wiring diagram.

8.2 Analog Controls

for Heating or

Heating/Makeup

Air

8.2.2 Two-Stage

Operation -

Recirculated Heating

Only (Option AG2 applies

to Model RDH and Model

RHH; Option EG2 applies

to Model REH)

On Models RDH and RHH, a two-stage combination gas control valve provides for

low fire (70%) or high fire (100%) operation controlled by a two-stage thermostat.

First stage (low fire) is factory set. Both high and low stages are controlled by a Servo

regulator, maintaining constant gas input under wide variations in gas supply pressure.

See instructions packed with the unit for specific gas valve specifications, wiring, and

operating instructions.

On a Model REH, staging of heat from the heating elements is controlled by the two-

stage thermostat.

A two-stage thermostat can either be selected as an option or be field supplied. Follow

the thermostat manufacturer’s instructions and the wiring diagram.