beautypg.com

3 unit wiring requirements and wiring diagrams, 4 control wiring – Reznor RXH (Outdoor PreevA) Unit Installation Manual User Manual

Page 45

background image

Form I-RDH/REH/RHH/RXH (12-14), P/N 215210 R14, Page 45

Each unit has a custom wiring diagram in the control compartment. All optional elec-

trical components ordered with the unit are shown on the wiring diagram. Codes for

options ordered are listed across the bottom of the diagram. To identify option codes,

see list in

APPENDIX, page 64.

CAUTION: If any of the original wire as supplied with the appliance

must be replaced, it must be replaced with wiring material having a

temperature rating of at least 105°C, except for sensor lead wires which

must be 150°C. See Hazard Levels, page 2.

7.3 Unit Wiring

Requirements

and Wiring

Diagrams

7.4 Control Wiring

The heater is equipped with a low voltage (24V) control circuit. Control wiring con-

nected to a thermostat, a switch, a discharge air temperature sensor, a remote tem-

perature selector or sensor, an amplifier, or the valve must not be run close to or inside

conduit with power or ignition wires.

7.4.1 Control Wiring

Requirements

IMPORTANT (but does not apply to ignition control board used with modulating controls AG58 and D12G): When using

a multimeter to troubleshoot the 24 volt circuit, place the meter’s test leads into the 5 or 9 pin connectors located on the

ignition control board

(FIGURE 52, page 58). Do not remove connectors or terminals from the electrical components.

Doing so can result in misinterpreted readings due to the ignition control board’s fault mode monitoring circuits.

TABLE 28 - 24V

Field Control Wiring

Length/Gauge

Total Wire Length

Distance from Unit to Control

Minimum Recommended Wire Gauge

150ft (46M)

75ft (23M)

18

250ft (76M)

125ft (38M)

16

350ft (107M)

175ft (53M)

14

Digital Control Signal Wiring Recommendations and Requirements

For optimum temperature control performance the manufacturer recommends that the

analog and digital inputs (zone sensors, discharge air sensors, etc.) connected to the

main controller (used in heating/cooling control DG and D12 Options) be routed to the

unit in one of the following manners:

1) In separate conduits, isolated from 24 VAC controls and line voltage power to the

unit,

OR

2) If the digital sensor wires are to be run in the same conduit as the 24 VAC control

wiring, the sensor wiring must be completed using shielded cable and bundled

separately from the 24 VAC control wiring. The shield must be drained at the unit

and taped on the opposite end.

See

TABLE 29 (left) for digital control sensor wire gauge and length requirements.

TABLE 29 - Maximum Digital

Control Sensor Wire Length for

less than 1°F Signal Error

Wire

Gauge

Maximum Sensor Wire

Length (Digital Control)

AWG

Feet

Meters

14

800

244

16

500

152

18

310

94

20

200

61

22

124

38

7.4.2 Analog or Digital

Controls

Type of control varies with option selection (identified on the unit wiring diagram). Con-

trol may be analog or digital depending on option selected. Option EG1, EG2, AG1,

AG2, AG3, AG15, AG16, AG58, AG60, AG61, and AG62 controls are analog; Option

DG1, DG2, DG5, DG6, D12B, D12C, D12D, D12E, and D12G controls are digital.

Option AG40 is designed for digital control from a field-supplied source. Optional con-

trols are identified on the wiring diagram supplied with the heater.

NOTES: All systems

with reheat Option AU7 have an Option D12 digital control.

Digital Control Systems

have a Programmable

Unit-Mounted Control

and a Room Command

Module

If using a digital control system, the unit is factory equipped with a programmable con-

troller.

Digital control Options DG1, DG2, DG5, and DG6 also include a room command mod-

ule. The type of room command module depends on whether the control system has

a discharge or a room temperature controlled setpoint. A room command module with

an adjustable room temperature setpoint (45°F - 95°F) included with Option DG1 and

DG2 control systems is illustrated in

FIGURE 40A, page 46. A room command module

with a discharge air setpoint included with Option DG5 and DG6 control systems is in

FIGURE 40B. The discharge air setpoint can be adjusted ±6°. Discharge temperature

controls may also have an optional room-mounted override sensor.

IMPORTANT: The digital controller inputs are low-current, resistance-based

signals. See special wiring recommendations above for digital sensor wiring.

Digital control Options D12B, D12C, D12D, D12E, and D12G do not include a room

command module. The space temperature sensor module with adjustable setpoint

control and room override illustrated in

FIGURE 40C is available as an option.