6.4 Unit Inlet Air

(Supply Air) -

Models RDH,

REH, RHH, and

RXH

Depending on how the unit was ordered, the blower can have a variety of factory-

installed and/or field-installed inlets. The cabinet end can be full open with or without a

screen; can have a factory-installed duct flange with or without a two-position damper,

or a field-installed hood. The blower inlet can have or not have a filter rack with filters.
Or, the blower cabinet inlet end can have an attached combination of modules includ-

ing a mixing box with either one or two inlets with duct flanges and a variety of controls,

a cooling coil module, and/or an evaporative cooling module.

6.0 Mechanical

(cont’d)

6.4.1 Optional Inlet

Duct Flange (factory

installed), Option AR5

X

Blower Cabinet

Inlet Air Opening

with Duct Flange

Option AR5

Y

3/4”(19mm)

3/4”(19mm)

3/4”

(19mm)

3/4”

(19mm)

TABLE 15 - Dimensions of Optional Inlet Air Duct Flange

RDH

REH

RHH

RXH

X

Y

75/100

10A/20A/

40A

N/A

000A

inches

24-1/2 25-1/16

mm

622

636

125/150 15B/30B/

60B

N/A

000B

inches

34-1/2 25-1/16

mm

876

636

175/200

/225

N/A

130/180 000C

inches

24-1/2 37-5/16

mm

622

948

250/300 30D/60D/

90D/120D

260

000D

inches

40-3/4 37-5/16

mm

1035

948

350/

400A

40E/80E/

120E

350

000E

inches

48-3/4 37-5/16

mm

1238

948

FIGURE 18A - Optional

Inlet Air Duct Flange

on the Blower Cabinet,

Option AR5

Dimensions for attaching ductwork are shown in

FIGURE 18A and TABLE 15. The

optional duct flange is 1-1/2” (38mm) long with a 3/4” (19mm) wide flange on all sides.
The inlet air duct should be attached and sealed. Ductwork must have a free area

equal to the duct connection.

6.4.2 Optional Two-Position Damper (factory installed), Option AR8 -

Models RDH, REH, RHH, RXH (requires Option AS2 Hood)

The illustration in

FIGURE 18B shows a two-position damper attached directly to the

blower cabinet. If ordered with a cooling coil module, the damper will be attached to the

inlet air end of the cooling coil module. Weight added is in

TABLE 5, page 10.

FIGURE 17A - Remove the

Cover from the Flue Outlet

Remove the screened box cover

on the vent outlet.

The box is attached on each side

with one screw. Remove the four

screws and the cover making the

vent pipe collar accessible.

Maximum

Height

8 feet

(2.4M)

C

L

Provides

4 ft (1.2M)

vertical

clearance

between

vent outlet

and fresh

air intake

Sizes 75-150

18-3/4”

(476mm)

Sizes

175-400A

28” (711mm)

Use existing screws in cabinet top to attach

two field-supplied angles to support the vent pipe.

Recommended angle material is 3/4” x 3/4” 20 gauge.

CC1 Vent

Cap

4” is

P/N 111848;

5” is

P/N 111849

Attach a minimum of 12”

(305mm) of straight vent

pipe to the collar.

RDH Size

Vent Connection

inches

mm

75, 100, 125, 150

4

102

175, 200, 225, 250,

300, 350, 400A

5

127

FIGURE 17B - Install a Vertical Vent Pipe and Cap - Maximum

height is 8 ft (2.4M).

TABLE 14 - Vent Connection Sizes

6.3.2 Venting Model RDH

A Model RDH vents through the screened “box” on the side of the heat section. If local

code requires 4-ft (1.2M) vertical clearance between the flue outlet and the fresh air

intake of the heating system or the building, install a vertical vent with an optional vent

cap. The option package includes the vent cap only. The vent pipe is field supplied.

The vent pipe should be the same size as the vent connection diameter listed below.

Remove the cover shown in

FIGURE 17A and follow the illustrated instructions in

FIGURE 17B.

6.3 Venting - Models

RDH and RHH

(cont’d)