beautypg.com

Dehumidification - models rdh, reh, rhh, and rxh, 0 controls and operation (cont’d) – Reznor RXH (Outdoor PreevA) Unit Installation Manual User Manual

Page 52

background image

Form I-RDH/REH/RHH/RXH (12-14), Page 52

FIGURE 46 -

Maxitrol

Signal Conditioner, P/N

134170, used in Options

AG40, DG2, and DG6

Optional Modulation Gas Control with Field-Supplied Controller (Option AG40) -

With this control, the modulation gas heating system is identical to digital Options DG2

and DG6 in Paragraph 8.3. The programmable digital controller is not supplied. The unit

is equipped with a Maxitrol signal conditioner (

FIGURE 46) that accepts an input signal

of either 4-20 milliamps or 0-10 volts from a field-supplied controller and converts it to

the 0-20 volt DC current required to control the modulating valve.Temperature selection

or building management is controlled by customer-supplied software.

8.0 Controls and

Operation (cont’d)

8.2.4 Constant Discharge Air Temperature with Maintained Thermal

Efficiency (cont’d)

8.3.1 Optional Digital Heating/Cooling/Makeup Air Controls, Options

DG1, DG2, DG5, DG6 - Model RDH only

Application NOTES: Options DG 1, 2, 5, and 6 do not apply to units with reheat pump

(dehumidification) Option AU7L or AU7R. Model RDH with Option AU7 requires D12B,

D12C, or D12G; see Paragraph 8.3.2.

8.3 Digital Controls

for Heating/

Cooling,

Makeup Air, and

Dehumidification -

Models RDH, REH,

RHH, and RXH

Digital control systems (Options DG1, DG2, DG5, and DG6) have a unit-mounted, factory-

wired, 24 volt, DDC programmable controller (

FIGURE 47); a venter speed control board

(

FIGURE 45); and a room command module (either FIGURE 48A or 48B). Options DG2

and DG6 with modulating gas heat have a Maxitrol conditioner (

FIGURE 46).

The four DG control sequences include a wall-mounted Fan/Heat/Cool/Auto Switch.
Option DG1 -

Room control with 2-stage gas heating and 3-stage cooling control. The

wall mount interface allows the user to adjust the space setpoint from 45°F to 95°F and
select the unit mode. Unit modes are Cool Only, Heat Only, Fan Only, Auto Mode, and Off.

Option DG2 -

Room control with 4:1 modulated gas heat and 3-stage cooling control.

The wall mount interface allows the user to adjust the space setpoint from 45°F to 95°F and
select the unit mode. Unit modes are Cool Only, Heat Only, Fan Only, Auto Mode, and Off.

Option DG5 -

Room control with 2-stage gas heating and 3-stage cooling control. The

wall mount interface allows the user to adjust the discharge air temperature ± 6°F from the
factory-mounted controller setpoint and select unit mode. Unit modes are Cool Only, Heat
Only, Fan Only, Auto Mode, and Off.

Option DG6 -

Room control with 4:1 modulated gas heat and 3-stage cooling control. The

wall mount interface allows the user to adjust the discharge air temperature ± 6°F from the
factory-mounted controller setpoint and select unit mode. Unit modes are Cool Only, Heat
Only, Fan Only, Auto Mode, and Off.

FIGURE 47 -

Programmable Digital

Controller, Johnson

Controls FX05 used in all

DG Options

For explanation on the

settings and functions of

the FX05 programmable

control, see Form CP-

PREEVA-DG with FX05.

The heating and cooling equipment will cycle to maintain the active heating discharge

or space temperature setpoint, based upon the unit mode and time of day schedule.

Optional Ductstat with Electronic Remote Setpoint Module (Options AG61 and

AG62) - The factory-installed sensing probe must be field-wired to the 0-120°F remote

temperature selector illustrated in

FIGURE 44B.

The remote modules are shipped separately for field installation. Follow the wiring

diagram with the unit and the manufacturer’s instructions for wiring and installation.

CAUTION: Be sure heat/cool selector switch is set at “Heat” position.

There will be one module for selecting temperature and one-stage adder module.

The optional digital display module is used only in Option AG62. See

FIGURE 44B.

Electronic Modulation between 50% and 100% Firing Rate (Options AG8, AG9 & AG9H)

Depending on the heat requirements as established by the thermistor sensor, the burner

modulates between 100% and 50% firing. The thermistor is a resistor that is temperature

sensitive in that as the surrounding temperature changes, the Ohms resistance changes

through the thermistor. This change is monitored by the solid state control center (ampli-

fier) which furnishes varying DC current to the modulating valve to adjust the gas input.
Each modulating valve is basically a regulator with electrical means of raising and lower-

ing the discharge pressure. When no DC current is fed to this device, it functions as a gas

pressure regulator, supplying 3.5" w.c. pressure to the main operating valve.
Refer to the wiring diagram supplied with the furnace for proper wiring connections.

Electronic modulation control systems for makeup air applications controlled by a field-

installed duct sensor (See Paragraph 6.7.3) and temperature selector (55-90°F) are

identified as either Option AG8 or Option AG9 & AG9H. The temperature selector set-

ting for Option AG8 is on the amplifier; Option AG9 & AG9H has a remote temperature

selector. Both systems are available with an override thermostat.

FIGURE 46B -

Amplifier in Options

AG8 (P/N 260864); AG9

and AG9H (P/N 260863

for both)

8.2.6 Optional Electronic Modulation

8.2 Analog Controls

for Heating or

Heating/Makeup

Air (cont’d)

8.2.5 Modulation Gas Control with Field Supplied Digital Control