beautypg.com

0 electrical supply and wiring, 1 general, 2 supply wiring – Reznor RXH (Outdoor PreevA) Unit Installation Manual User Manual

Page 43: 3 blower rotation, 4 optional variable frequency drive (vfd)

background image

Form I-RDH/REH/RHH/RXH (12-14), P/N 215210 R14, Page 43

6.9.3 Blower Rotation

Rotation may be changed on single-phase motors by re-wiring in the motor terminal

box. Three-phase motors may be reversed by interchanging two wires on the 3-phase

supply connections.

6.9.4 Optional Variable Frequency Drive (VFD)

If ordered with a VFD, it may be either factory or field

installed. If field-installed, follow the manufacturer’s instruc-

tions and refer to the wiring diagram on the unit. Minimum

ambient temperature for a VFD is 18°F. Maximum distance

from the unit is 50 feet.
When an optional VFD is ordered, the motor operates on

two speeds as determined by the electrical frequency.

High speed is used for cooling and low speed for heating.

60 hertz is the maximum high speed. Maximum speed for

low speed heating is the frequency that will provide the

maximum temperature rise of the heater.
Maximum allowable temperature rise for a Model RDH is

70°F with an aluminized heat exchanger or 100°F with a

stainless steel heat exchanger. (

NOTE: If equipped with

modulating gas control Option AG40, AG58, DG2, DG6,

D12B, or D12G and a stainless steel heat exchanger, a

maximum temperature rise of 120°F is permitted.)
Follow the VFD controller manufacturer’s instructions that

are packaged with the heater (in the owner’s envelope) to

program the VFD settings. The formula for motor speed is

N=120xf/p where N is speed; f is frequency; and p is num-

ber of poles (3600 RPM motor has 2 poles; an 1800 RPM

motor has 4 poles).
Example: 1800 RPM motor on 60Hz; N = 120 x 60/4 =

1800

1800 is synchronous speed; assume 2% slip.

Motor will run

between 1750

and 1790 RPM at full load depending on design.

Run the same motor at 45Hz (120 x 45/4

= 1350). 1350 RPM

less 2% slip equals about 1300 RPM.

7.0 Electrical Supply

and Wiring

7.1 General

All electrical wiring and connections including electrical grounding must be made in

accordance with the National Electric Code ANSI/NFPA No. 70 (latest edition) or, in

Canada, the Canadian Electrical Code, Part I-C.S.A. Standard C22.l. Check any local

ordinances or utility company requirements that apply.
Check the rating plate on the heater for the supply voltage and the current require-

ments. A separate line voltage supply with fused disconnect switch should be run

directly from the main electrical panel to the unit, making connections in the electrical

compartment. Supply wiring enters the cabinet either on the control side below the

electrical compartment door or in line directly below through the base.

Seal all electri-

cal entrance openings with field-supplied bushings.

Before turning on the power, check and tighten all electrical terminals.

7.2 Supply Wiring

NOTE: If the system has an

optional convenience outlet

or UVC light, both of those

options require a separate

115 volt power supply.

Field-Supplied Wiring Size - Models RDH, RHH, and RXH

Voltage/Phase

115/1

208-230/1

208-230/3

460/3

575/3

Motor HP's

1/4 - 1/2

1

1 - 1-1/2

1/4 - 3

5

1/4 - 5

1/2 - 5

Wire Gauge

14

12

14

14

12

14

14

BX Cable

3/8"

3/8"

3/8"

3/8"

3/8"

3/8"

3/8"

TABLE 27A - Supply

Wiring Size - Models

RDH, RHH, and RXH

Field-Supplied THHN, THWN or THWN-2 Wiring and Conduit Minimum Size for Model REH

Voltage/Phase

208/1

230/1

KW

10

15

20

30

10

15

20

30

Ampacity

74

96

119

164

78

104

130

182

75°C Wire Gauge

#4

#3

#1

#2/0

#4

#2

#1

#3/0

Conduit Trade Size

1

1

1-1/4 1-1/2

1

1

1-1/4

2

Voltage/Phase

208/3

230/3

KW

20

30

40

60

80

90

120

20

30

40

60

80

90

120

Ampacity

66

92

118

142

184

205

267

74

104

134 161 209

233

305

75°C Wire Gauge

#4

#3

#1

#1/0 #3/0 #4/0 300kcmil #4

#2

#1/0 #2/0 #4/0 250kcmil 350kcmil

Conduit Trade Size

1

1-1/4 1-1/2 1-1/2

2

2

2-1/2

1

1-1/4 1-1/2

2

2

2-1/2

3

Voltage/Phase

460/3

575/3

KW

20

30

40

60

80

90

120

20

30

40

60

80

90

120

Ampacity

37

52

67

81

105

117

153

31

44

56

67

88

98

128

75°C Wire Gauge

#8

#6

#4

#4

#2

#1

#2/0

#10

#8

#6

#4

#3

#3

#1

Conduit Trade Size

3/4

3/4

1

1

1-1/4 1-1/2

2

1/2

3/4

3/4

1

1-1/4

1-1/4

1-1/2

TABLE 27B -

Supply

Wiring Size -

Model REH

7.2.1 Supply Voltage

The electric supply to the unit must meet stringent requirements for the system to oper-

ate properly. Voltage supply should be within ±10% or as stated on the rating plate.

Maximum imbalance on a 3-phase system is 2%. Follow instructions below to check.