beautypg.com

3 venting - models rdh and rhh – Reznor RXH (Outdoor PreevA) Unit Installation Manual User Manual

Page 23

background image

Form I-RDH/REH/RHH/RXH (12-14), P/N 215210 R14, Page 23

6.2.3 Heat Section Condensate Drains - Model RHH High Efficiency Unit

FIGURE 15 -

Bottom

View of a

Model RHH

showing

Location

of the Heat

Section

Condensate

Drains

(A)

(B)

Insulate tubing

and attach it into

the drain at

the “T”.

Parts Provided (Shipped Separately) for

Installing Condensate Drains

P/N

Description

271064 Freeze-Resistant Condensate Drain Trap

205037 1/2” Schedule 40 Tee

105944 1/2” Schedule 40 Female Adapter

105948 1/2x1/2 Nylon Hose Barb (male)
271183 36” length of pipe insulation (for insulating

the drain hose)

271184 36” length of pipe insulation (for insulating

the 1/2” PVC drain pipe)

Instructions for Installing Model RHH

Heat Section Condensate Drains

NOTE: All PVC drain pipe is provided by the

installer. Depending on the installation, a field-

provided or optional heat tape may be needed.

6.3 Venting - Models

RDH and RHH

6.3.1 Venting - Model RHH

Model RHH has a high efficiency condensing heat section. The heat section vents

through a Schedule 40 PVC pipe that extends from the side of the unit as shown

in

FIGURE 16. The vent must be terminated with an installer-provided 45° elbow of

Schedule 40 PVC or CPVC vemt pipe.

NOTE: In Canada, all PVC vent pipe must be

approved to ULC S636.
Attach the elbow in the orientation illustrated so that the flue products are directed

downward.

FIGURE 16 - Terminate the

vent with a 45° Schedule 40

PVC elbow in the orientation

illustrated. Flue products must

be directed downward.

1) Determine the length of field-provided 1/2” PVC pipe needed

at

(A). At location (A), connect the PVC pipe to the coupler

on the condensate drain in the unit. Slide the pipe insulation

(shipped-separate parts above) over the 1/2” PVC pipe and up

over the joint at

(A). Secure the insulation so that it will continue

to cover the joint at

(A). Cut off any excess.

Freeze

Resistant

Trap,

P/N 271064

2) At the end of the pipe, location (B), position the Schedule 40 tee (from

shipped-separate parts) as illustrated and attach. Extend the tubing from

the second drain toward the tee. Determine the length of PVC pipe needed

to allow the tubing to be attached. Attach the length of PVC pipe to the tee.

From the shipped-separate items, attach the female adapter to the pipe

and the hose barb to the adapter. Slide the smaller piece of insulation over

the tubing and up into the unit. Secure

the insulation. Attach the thetubing to

the hose barb.

3) Attach PVC drain to the “T”. Downstream from the “T”,

install the freeze resistant trap,

P/N 271064 (shown right).

Follow the manufacturer’s instructions to install and maintain

the trap. Continue the line from the trap into a sanitary drain.