Form I-RDH/REH/RHH/RXH (12-14), P/N 215210 R14, Page 5

Field-Installed Accessories

- If your unit was ordered with Option UV2, UVC lights

in the cooling coil module, the bulbs and a box of parts are shipped in the blower com-

partment for field installation. Being careful not to touch the bulbs, verify the compo-

nents with the instruction sheet included with the parts.
Before beginning installation, be sure that all shipped-separate options ordered are

available at the site. Field-installed, shipped-separate options could include a roof

curb, an outside air hood, a vent cap, an energy recovery unit, a VFD, a thermostat

or other wall-mounted control, a remote console, a disconnect switch, a fill and drain

or freeze protection kit, a water hammer arrestor, a firestat, and/or a smoke detector.

Storage and Startup -

If this unit is going to be stored, take precautions to prevent

condensate formation inside the electrical compartments and motors. To prevent dam-

age to the unit, do not store sitting on the ground.
After the system has been moved to its installation site, remove all of the shipping

brackets and check the blower for free movement. See the check lists in Paragraph 9.0

before starting the unit and completing the Startup Form.

TABLE 1- Shipped-Separate or Shipped-Loose Components for Factory-Installed Options

4.0 Clearances and

Dimensions

4.1 Clearances

For safety and convenience, provide clearances as shown in the following table.

Clearance to combustibles is defined as the minimum distance from the heater to a

surface or object that is necessary to ensure that a surface temperature of 90°F above

the surrounding ambient temperature is not exceeded. Minimum clearances are also

listed on the heater rating plate.

TABLE 2A - Minimum

Clearances from

Combustible Material

Recommended Service Clearances by Model and Size

Model and Size

Control Side

Side

Opposite

Controls

Top

RDH

REH

RHH

RXH

Control Side

(Basic)

Control Side with

Mixing Box

Control Side with

Cooling Coil*

inches

mm

inches

mm

inches

mm

inches

mm

inches

mm

75/100

10A/20A/30A

--

000A

30

762

30

762

42

1067

6

152

18

457

125/150

15B/30B/60B

--

000B

34

864

34

864

52

1321

6

152

18

457

175/200/ 225

N/A

130/180 000C

30

762

30

762

42

1067

6

152

24

610

250/300

30D/60D/90D/120D

260

000D

42

1067

42

1067

58

1473

6

152

24

610

350/400A

40E/80E/120E

350

000E

52

1321

52

1321

66

1676

6

152

24

610

Minimum Clearances to Combustibles - ALL Sizes of Models RDH, REH, RHH

Control Side Side Opposite Controls

Front

Rear

Top

Bottom

inches

20

6

48

18

6

0

mm

508

152

1219

457

152

0

TABLE 2B - Recommended Service Clearances

*Clearance is

required for sliding out drain pan.

Factory-Installed

Option

Option Parts Requiring Installation (Parts are either shipped loose with the heater or shipped separately.)

AG3, AG60

On/Off Control Switch,

P/N 39732; Discharge Air Sensor Holder, P/N 115850; Discharge Air Sensor Holder Bracket,

P/N 213612

AG15, AG61

On/Off Control Switch,

P/N 39732; Remote Ductstat Temperature Selector, P/N 115848; Stage Adder Module(s),

P/N 115849; Discharge Air Sensor Holder, P/N 115850; Discharge Air Sensor Holder Bracket, P/N 213612

AG16, AG62

On/Off Control Switch,

P/N 39732; Remote Temperature Selector, P/N 115848; Stage Adder Module(s), P/N 115849;

Digital Temperature Display,

P/N 115852; Discharge Air Sensor Holder, P/N 115850; Discharge Air Sensor Holder

Bracket,

P/N 213612

DG1, DG2

Room Command Module,

P/N 211423

DG5, DG6

Room Command Module,

P/N 211424; Discharge Air Sensor Holder, P/N 115850; Discharge Air Sensor Holder

Bracket,

P/N 213612

AG58, D12B, D12C,

D12D, D12E, D12G Discharge Air Sensor Holder, P/N 115850; Discharge Air Sensor Holder Bracket, P/N 213612

GE10

Potentiometer,

P/N 16110

GE15

Pressure Null Switch,

P/N 88052

GE21

Enthalpy Sensor and Parts to install,

P/N 220686

GE22

Two Enthalpy Sensors and Parts to install, (2)

P/N 220686

AU7L, AU7R

Duct Humidity/Temperature Sensor,

P/N 206081; Mounting Bracket, P/N 207499

(

NOTE: These will be factory installed if mixing box, Option MXB1, is ordered.)