beautypg.com

0 mechanical (cont’d) – Reznor RXH (Outdoor PreevA) Unit Installation Manual User Manual

Page 30

background image

Form I-RDH/REH/RHH/RXH (12-14), Page 30

Enthalpy Sensor(s)

Installation

Instructions:

NOTE: Attach the outside

air sensor when installing

the outside air hood; see

FIGURE 19B, pages 25-26.

1. Turn off the power (RDH, REH, RHH, RXH) and the gas (RHH and RDH).
2. Install the Outside Air Enthalpy Sensor - Option GE21 and Option GE22
a)

Attach the Sensor to the Outside Air Hood - On the same side as the electrical

box in the mixing box, position the sensor on the inside of the side of the outside

air hood (see

FIGURE 19B, pages 25-26). The sensor may be mounted in any

orientation but must be located so that it is exposed to freely circulating air and

must be protected from rain, snow, and direct sunlight. Position the sensor in a

central location on the side of the hood and attach with the two screws provided.

b)

Wire the Sensor - Connect the two wires to the sensor as shown on the wiring

diagram. Drill a 5/8” hole in the outside air damper mounting frame as illustrated in

FIGURE 24A. Insert the strain relief bushing. Bring the wires through the opening

and route them to the bottom of the electrical box. Use the stick-on wire holders

to prevent the wires from interfering with the damper operation. Insert a strain

relief bushing in a hole in the bottom of the electrical box and route the wires

through. Make connections at the economizer logic module as shown on the wiring

diagram.

Installation of Option GE21 control is complete. Refer to

FIGURES 24B and 24C to set

the enthalpy control (economizer logic module). If installing a return air sensor (Option

GE22), continue to Step 3.

Options GE21 and GE22 - Drill a

5/8” hole in the outside air

damper mounting frame.

Option GE22 - Drill a

5/8” hole in the return air

damper mounting frame.

Economizer

Logic Module,

P/N 220637

FIGURE 24A - Mixing Box

with Optional Economizer

Logic Module

3. Install the Return Air Enthalpy Sensor in the Return Air

Duct - Option GE22

a)

Attach the Sensor - On the same side as the electrical

box in the mixing box, position the sensor on the inside

of the return air duct. The sensor may be mounted in any

orientation but must be located so that it is exposed to freely

circulating air. Position the sensor in a central location on the

side of the duct and attach with the two screws provided.

b)

Wire the Sensor - Connect the two wires to the sensor as

shown on the wiring diagram. Drill a 5/8” hole in the return air

damper mounting frame as illustrated in

FIGURE 24A. Insert

the strain relief bushing. Bring the wires through the opening

and route them to the bottom of the electrical box. Use the

stick-on wire holders and the wire ties to prevent the wires

from interfering with the damper operation. Insert a strain

relief bushing in a hole in the bottom of the electrical box and

route the wires through. Make connections at the economizer

logic module as shown on the wiring diagram.

Installation of Option GE22 control is complete. Refer to

FIG-

URES 24B and 24C to set the economizer logic module.

Operating Sequence with Economizer

Option

On a call for low stage cooling
1. The blower motor is energized.
2. With the outdoor enthalpy less than the

return air enthalpy:

a) The stage 1 and 2 cool circuits are locked

out.

b) Dampers are positioned by the

economizer and mixed air sensor.

3. With outdoor air enthalpy higher than the

return air enthalpy:

a) The stage 1 cool circuit is energized.
b) Dampers are positioned for minimum

outside air.

c) On a call for high stage cooling, the stage

2 and 3 circuits are staged appropriately.

6.0 Mechanical

(cont’d)

6.4 Unit Inlet Air (cont’d)

6.4.5.3 Mixing Box Damper and Control Options

(cont’d)