beautypg.com

Reznor RXH (Outdoor PreevA) Unit Installation Manual User Manual

Page 33

background image

Form I-RDH/REH/RHH/RXH (12-14), P/N 215210 R14, Page 33

Evaporative

Cooling

Module

(factory attached)

Inlet Water Connection

(1/2” male NPT fitting)

Overflow Fitting

3/4” male NPT tapped

with 1/2” female NPT

Drain Fitting

3/4” male NPT tapped

with 1/2” female NPT

2-Way Solenoid Valve

(normally open)

1/2” female NPT

(A 2-way valve is in

Options CT1, CT2, and CT3.

Option CT6 requires

Option CT1, CT2, or CT3.)

To Drain

3-Way Solenoid Valve (valve is suitable for

a maximum close-off pressure differential

of 25 psi and a system static pressure of 300

psi) - 1/2” NPT, 2-position spring return

(normally closed at B port)

(A 3-way valve is in Options CT1, CT2, CT3,

and CT5. Option CT6 requires Option CT1,

CT2, or CT3.)

Actuator must be above the

valve body when mounted

in horizontal piping.

Roof

Water Inlet

Field-supplied

Service Valve

Field-supplied Pressure

Regulator (if required)

A

A

B

B

C

= Field-installed Water Piping

Left Side View

FIGURE 26 - Field-installed

optional Fill and Drain

Valves for Pump and Float

System (Option CT1, CT2, or

CT3)

and

Freeze Protection Kits

(Option CT5 for AquaSaver

and Option CT6 for Pump

and Float System)

Sequence of Operation

with Optional Fill and

Drain and/or Freeze

Protection Kits

Applies to: Float and Pump System with Optional

Fill and Drain Kit (Option CT1, CT2, or CT3)

1) Call for cooling.

2) 2-way valve is energized and closes B to A.

3) 3-way valve is energized opening B to C and closing A to C.

4) During no call for cooling, valves return to normal state.
Applies to: AquaSaver Timed Water System with Optional Freeze Protection (Option CT5)

1) Call for cooling.

2) 3-way valve is energized opening B to C and closing A to C.

3) If outside air temperature drops below freeze protection controller setting, 3-way valve is de-energized and

AquaSaver 24V solenoid valve remains energized for eight minutes to allow complete system water drainage.

4) During no call for cooling, 3-way valve returns to normal state.
Applies to: Float and Pump System with Optional Fill and Drain Kit (Option CT1, CT2, or CT3) and Freeze

Protection (Option CT6)

1) Call for cooling.

2) 2-way valve is energized and closes B to A.

3) 3-way valve is energized opening B to C and closing A to C.

4) If outside air temperature drops below freeze protection controller setting, valves return to normal state.

5) During no call for cooling, valves return to normal state.

tion (above 32°F), either horizontal or vertical, in line with and as close to the solenoid

valve as possible. Follow the manufacturer’s instructions to install and maintain the

water hammer arrestor.
Recirculating Float and Pump Control System - Turn on the water supply and check

for good flow. When the float valve (

FIGURE 27) shuts off the water supply, measure

the water depth. The depth of the water should be approximately 3” (76mm). If neces-

sary, adjust the position of the float valve with the wing nut to obtain the proper water

level.

Adjust the float valve position with the wing nut to

maintain approximately 3” (76mm) of water in the

reservoir

.

1/2” MPT Water Supply Connection

FIGURE 27 - Float

Valve, P/N 216553