Roof Curb Assembly

and Installation

Instructions

(See layout in FIGURE 8 and
illustrations in FIGURE 9.)

FIGURE 9 - Roof Curb Assembly

Unit

Bottom

MUST be sealed between

curb cap and roof curb

Unit

Base

Wood Nailer

Insulation

6-1/4”

(159mm)

Counter Flashing

(by installer)

Roofing Felts and Cant

Strip (by installer)

Weld, bolt or lag screw

curb to deck structure.

16”

(406mm)

1-7/8”(48mm)

(102mm)

2 x 6 Wood

Nailer

1-1/2 x 3 lb

Fiberglass

Flashed by the

installer (flashing

must be under

lip of curb)

Lag Screw

and Washer

Cap

Screws

Curb and Curb Cap Detail

Curb Section

Corner Detail

5.0 Mounting and

Lifting (cont’d)

5.2.3 Mounting on a Roof Curb (cont’d)

5.2 Mounting (cont’d)

TABLE 9A - Dimensions and Weights of Optional Roof Curbs for Model RHH (See FIGURE 8, pg 12.)

Configuration*

Option

Code

RHH

Inches (±1/8)

mm (±3)

Weight

A

B

C

D

A

B

C

D

lbs

kg

Model RHH and horizontal discharge

CJ8Q

130/180 77-1/2 29-13/16

73-3/4

26-1/16 1,969 757 1,873 662

260

77-1/2

46-1/16

73-3/4

42-5/16 1,969 1,170 1,873 1,075

350

77-1/2

54-1/16

73-3/4

50-5/16 1,969 1,373 1,873 1,278

Model RHH PLUS 1 either Downturn Discharge Plenum

(AQ5 or AQ8); OR Mixing Box (MXB1) with horizontal

discharge; OR Cooling Coil Cabinet without Reheat (AU5

or AU6) with horizontal discharge

CJ8R

130/180 105-1/4 29-13/16 101-1/2 26-1/16 2,673 757 2,578 662

260

105-1/4

46-1/16

101-1/2

42-5/16 2,673 1,170 2,578 1,075

350

105-1/4

54-1/16

101-1/2

50-5/16 2,673 1,373 2,578 1,278

Model RHH PLUS 2 - Down Discharge (AQ 5 or AQ8) AND

Mixing Box OR Cooling Coil Cabinet without Reheat (AU

5 or 6); OR Mixing Box AND Cooling Coil Cabinet without

Reheat (AU 5 or 6) with horizontal discharge

CJ8S

130/180

133

29-13/16 129-1/4 26-1/16 3,378 757 3,283 662

260

133

46-1/16

129-1/4

42-5/16 3,378 1,170 3,283 1,075

350

133

54-1/16

129-1/4

50-5/16 3,378 1,373 3,283 1,278

Model RHH PLUS 3 - Down Discharge Plenum (AQ5 or

AQ8) AND Mixing Box (MXB1) AND Cooling Coil Cabinet

without Reheat (AU5 or AU6)

CJ8T

130/180 160-3/4 29-13/16

157

26-1/16 4,083 757 3,988 662

260

160-3/4

46-1/16

157

42-5/16 4,083 1,170 3,988 1,075

350

160-3/4

54-1/16

157

50-5/16 4,083 1,373 3,988 1,278

Model RHH PLUS 1 - Cooling Coil Cabinet with Reheat

(AU7) with horizontal discharge

CJ8U

130/180 130-1/4 29-13/16 126-1/2 26-1/16 3,308 757 3,213 662

260

130-1/4

46-1/16

126-1/2

42-5/16 3,308 1,170 3,213 1,075

350

130-1/4

54-1/16

126-1/2

50-5/16 3,308 1,373 3,213 1,278

Model RHH PLUS 2 - Cooling Coil Cabinet with Reheat

(AU7) AND Down Discharge Plenum (AQ5 or AQ8) OR

Mixing Box (MXB1) with horizontal discharge

CJ8V

130/180

158

29-13/16 154-1/4 26-1/16 4,013 757 3,918 662

260

158

46-1/16

154-1/4

42-5/16 4,013 1,170 3,918 1,075

350

158

54-1/16

154-1/4

50-5/16 4,013 1,373 3,918 1,278

Model RHH PLUS 3 - Cooling Coil Cabinet with Reheat

(AU7) AND Down Discharge Plenum (AQ5 or AQ8) AND

Mixing Box (MXB1)

CJ8W

130/180 185-3/4 29-13/16

182

26-1/16 4,718 757 4,623 662

260

185-3/4

46-1/16

182

42-5/16 4,718 1,170 4,623 1,075

350

185-3/4

54-1/16

182

50-5/16 4,718 1,373 4,623 1,278

TABLE 9B - Dimensions for Locations

of Bottom Duct Connections as shown

in FIGURE 8 for Model RHH

Important NOTE: To ensure proper operation of a

Model RHH, the opening through the roof must be

the same area as the inside dimension of the roof

curb.

Inside area of the roof curb under a Model

RHH must be open.

Model

RHH

Duct Location Dimensions (inches ±1/8)

Duct Location Dimensions (mm ±3)

F

H

K (w/mixing box & downturn)

F

H

K (w/mixing box & downturn)

(with mixing box

and/or down

discharge)

no

cooling

coil

module

with a cooling coil

module

(with mixing

box and/

or down

discharge)

no

cooling

coil

module

with a cooling coil

module

no

reheat

with

reheat

no

reheat

with

reheat

130/180 22-7/8 1-9/16 107-3/8 135-1/8 160-1/8

581

40

2727

3432

4067

260

34-3/4

3-3/4 107-3/8 135-1/8 160-1/8

883

96

2727

3432

4067

350

45-13/16 2-1/4 107-3/8 135-1/8 160-1/8 1164

57

2727

3432

4067

Curbs are shipped unassembled. Field assembly and mounting on the roof are the

responsibility of the installer. All hardware necessary to assemble the curb is supplied.

Additional installation hardware must be field supplied.
IMPORTANT: Before installing roof curb, verify that the size is correct for the

system being installed.

* See Configurations in Paragraph 4.2.

NOTE: If there is an evaporative cooling module, the base of the unit under the evaporative cooling

module extends beyond the end of the roof curb. An evaporative cooling module does not affect the length of the roof curb.