beautypg.com

5 electrical operating components, Cl33, Cl52 – Reznor RXH (Outdoor PreevA) Unit Installation Manual User Manual

Page 46: Cl22, Cl36, Cl23, 0 electrical (cont’d), 4 control wiring (cont’d), 1 high temperature limit control - rdh/rhh, Rdh & rhh w/ag58)

background image

Form I-RDH/REH/RHH/RXH (12-14), Page 46

If using an analog control system, use either an optional or a field-provided low-voltage

(24V) thermostat. (A thermostat is not supplied.) Install the thermostat according to the

manufacturer’s instructions. Depending on the control system option, select either a

single-stage or two-stage thermostat.

Analog Control System

Requires an Optional

or Field-Supplied

Thermostat

FIGURE 41 - 24V Single-Stage and Two-Stage Thermostat Wiring

NOTES:

1) JUMPER THERMOSTAT TERMINALS RH TO RC.

FIELD WIRING

(USE

WITH AG2)

TWO ST

AGE HEA

T/COOL

THERMOST

AT W/F

AN SWITCH

(SEE NOTE #1)

G

W1

W2

Y2

Y1

RC

RH

RH

(SEE NOTE #1)

A1

G

W2

W1

Y2

Y1

X

A2

RC

G

W2

W1

Y2

Y1

C

R

TERMINAL

STRIP

G

W1

W2

Y2

Y1

C

R

TERMINAL

STRIP

CL33

P/N 221038

CL52

P/N 220632

CL22

P/N 220630

CL22

P/N 220630

SINGLE ST

AGE THERMOST

AT

TERMINAL

STRIP

G

W2

W

W1

Y2

Y1

C

R

R

CL1

P/N 255350

W2

TWO ST

AGE HEA

T/COOL

THERMOST

AT W/F

AN SWITCH

TERMINAL

STRIP

G

W2

G

Y1

(SEE NOTES #1

AND #2)

W1

Y2

W1

Y2

RC

RH

Y1

C

R

(RECIRCULATING AIR) (MAKE-UP AIR)

14

IN HEAT

SECTION

TERMINAL

BLOCK

G

W

Y

R

RC

(SEE NOTE #1)

G

W1

W2

Y2

Y1

C

TERMINAL

STRIP

R

SINGLE ST

AGE PROGRAMMABLE THERMOST

AT

TWO ST

AGE PROGRAMMABLE THERMOST

AT

C

C

2) SET FAN CONTROL FUNCTION TO "ELECTRIC FURNACE".

BK

(Ref WD 226260)

CL36

(RDH & RHH

w/AG58)

P/N 257600

CL23

(RDH & RHH)

P/N 257338

IN HEAT

SECTION

TERMINAL

BLOCK

W2

TWO ST

AGE HEA

T/COOL

PROGRAMMABLE THERMOST

AT

TERMINAL

STRIP

G

W2

G

Y

W

Y2

W1

Y2

RC

R

Y1

C

R

14

C

BK

S2

S1

A

Y1

Y2

G

W1

R

W2

C

THERMOSTAT
TERMINAL STRIP
(NOT IN
SEQUENCE)

X

RC

RH

W1

G

MX

MH

AS

AS

DISCHARGE

AIR SENSOR

Y1

(USE WITH

AG3,15,16,60,61,62)

PROGRAMMABLE MODULA

TING HEA

TING/COOLING

THERMOST

AT

(SEE NOTE #1.)

If ordered with an optional expansion card, a digital control system will provide week-

day and weekend scheduling of start/stop operation or interface to a field-supplied

Johnson N2 or Lonmark building automation system.

See the control instruction manual for additional information.

FIGURE 40A - Room

Command Module, P/N

211423, Sensing Space

Temperature for Digital

Controls, Option DG1

and DG2

FIGURE 40B - Room

Command Module,

P/N 211424, Sensing

Discharge Temperature

for Digital Controls,

Option DG5 and DG6

FIGURE 40C - Room

Command Module, Option

CL67, P/N 260599 Sensing

Discharge Temperature for

Digital Controls, Options

D12B, D12C, D12D, D12E,

D12G

All units are equipped with a temperature activated auto reset capillary-type limit con-

trol. The control is factory set and is non-adjustable. If the setpoint is reached, the limit

control will interrupt the electric supply to the gas valve. This safety device provides

protection in the case of motor failure or lack of airflow due to a restriction at the inlet

or outlet.

7.5.1 High Temperature Limit Control - RDH/RHH

7.5 Electrical

Operating

Components

CAUTION: The auto reset limit control will continue to shut down the heater until the cause

is corrected. Never bypass the limit control; hazardous conditions could result. See Hazard

Intensity Levels, page 2.

7.0 Electrical

(cont’d)

7.4 Control Wiring

(cont’d)

7.4.2 Analog or Digital

Controls (cont’d)

Digital Control Systems (cont’d)