beautypg.com

0 mechanical (cont’d), 4 unit inlet air (cont’d), Step 3 - install louver rack – Reznor RXH (Outdoor PreevA) Unit Installation Manual User Manual

Page 26: Step 4 - install screen, 4 optional filter rack and filters, Table 16 - filter quantity and sizes, 1 mixing box configurations, Table 17 - inlet air filter pressure drops, 3 screened outside air hood, option as2 (cont’d)

background image

Form I-RDH/REH/RHH/RXH (12-14), Page 26

STEP 3 - Install

louver rack.

Screen

Retainer

(part of

assembled

louver rack)

3a) Position the

louver rack in

the hood opening.

3b) Attach the louver

rack as shown with

sheetmetal screws.

Repeat on the other side.

STEP 4 - Install

screen.

4b) Attach screen clamp with three sheet-

metal screws. Repeat procedure on the

other side to install second screen clamp.

Outside air hood installation is complete.

Louver Rack

4a) Position

the screen and

the screen clamp.

Screen

INSTALLATION NOTE: If the installation includes damper control Option GE21 or GE22 that requires field installation

of a sensor in the outside air inlet, attach the sensor and connect the wires

before STEP 3 below. See Instructions on

page 29.

Filter rack and filters are factory-installed optional equipment. Depending on which

option was ordered, filters may be 2” disposable, 2” or 4” pleated disposable, or 2”

permanent.

6.4.4 Optional Filter

Rack and Filters

RDH Sizes

75, 100

125, 150 175, 200, 225

250, 300

350, 400A

REH Sizes

10A, 20A,

40A

15B, 30B,

60B

N/A

30D, 60D,

90D, 120D

40E, 80E, 120E

RHH Sizes

N/A

N/A

130, 180

260

350

RXH Sizes

000A

000B

000C

000D

000E

Filters - (Qty)

W x H in inches

(2)

16 x 25

(2)

20 x 25

(2) 16 x 16;

(2) 16 x 20

(3) 16 x 16;

(3) 16 x 20

(1) 16 x 16; (2) 20 x 20;

(3) 16 x 20

TABLE 16 - Filter

Quantity and Sizes

(Quantity and width and

height dimensions apply

to all type and thickness of

filters.)

6.4.5 Optional Mixing

Box (factory-installed) -

RDH, REH, RXH

If installation includes an Option MXB1 mixing box, it is factory installed in one of the

configurations illustrated in

FIGURE 20.

6.4.5.1 Mixing Box Configurations

All mixing box inlet air openings have a duct flange. (See dimensions in

FIGURE 22.)

All inlet air ducts should be attached and sealed. Return air duct must have a free area

equal to the return duct connection. See mixing box configurations in

FIGURE 20.

TABLE 17 - Inlet Air

Filter Pressure Drops

Pressure Drops for Clean Factory-Installed Filters by Type and Size ("w.c.)

Size CFM

Disposable Permanent

Aluminum

Pleated

Disposable

Size

CFM

Disposable Permanent

Aluminum

Pleated

Disposable

Size

CFM

Disposable Permanent

Aluminum

Pleated

Disposable

2''

2''

2''

4''

2''

2''

2''

4''

2''

2''

2''

4''

RDH

75,

100;

REH

10A,

20A,

40A;

RXH

000A

569

0.0

0.0

0.0

0.0

RDH

175,

200,

225;

RHH

130,

180;

RXH

000C

1329

.1

0.0

.1

0.0

RDH

350,

400A;

REH

40E,

80E,

120E;

RHH

350;

RXH

000E

2657

.1

0.0

.1

0.0

1650

.1

0.0

.1

0.0

3300

.1

0.0

.1

0.0

1000

.1

0.0

.1

0.0

2000

.1

0.0

.1

.1

3500

.1

0.0

.1

.1

2500

.1

.1

.1

.1

4000

.1

0.0

.1

.1

1500

.1

0.0

.1

.1

3000

.1

.1

.2

.1

4500

.1

.1

.1

.1

3500

.2

.1

.2

.2

5000

.1

.1

.2

.1

1898

.1

.1

.2

.1

4000

.2

.1

.3

.2

5500

.2

.1

.2

.1

4271

.2

.1

.3

.2

6000

.2

.1

.2

.1

RDH

125,

150;

REH

15B,

30B,

60B;

RXH

000B

949

0.0

0.0

0.0

0.0

RDH

250,

300;

REH

30D,

60D,

90D,

120D;

RHH

260;

RXH

000D

1898

.1

0.0

.1

0.0

6500

.2

.1

.2

.2

2050

.1

0.0

.1

0.0

7000

.2

.1

.3

.2

1250

.1

0.0

.1

0.0

2500

.1

0.0

.1

0.0

7400

.2

.1

.3

.2

3000

.1

0.0

.1

.1

7593

.3

.1

.3

.2

1500

.1

0.0

.1

0.0

3500

.1

0.0

.1

.1

4000

.1

.1

.1

.1

2000

.1

0.0

.1

.1

4500

.1

.1

.2

.1

5000

.2

.1

.2

.1

2500

.1

.1

.2

.1

5500

.2

.1

.2

.2

2847

.2

.1

.2

.1

5694

.2

.1

.3

.2

6.0 Mechanical

(cont’d)

6.4 Unit Inlet Air (cont’d)

6.4.3 Screened Outside Air Hood, Option AS2 (cont’d)

If the system does not have an optional cooling coil module, the vertical filter rack is

located in the entering air side of the blower cabinet. If the system has an optional

draw-through cooling coil module, the filter rack is located in the entering air side of

the cooling coil module.

FIGURE 19B - Outside Air Hood Assembly STEPS (cont’d)