beautypg.com

Reznor RXH (Outdoor PreevA) Unit Installation Manual User Manual

Page 21

background image

Form I-RDH/REH/RHH/RXH (12-14), P/N 215210 R14, Page 21

High Altitude Capacity Changes for Model RDH with Gas Control Option AG1, AG2, AG3, AG8, AG9, AG9H,

AG15, AG16, AG40, AG60, AG61, AG62, DG1, DG2, DG5, DG6, D12B, or D12C and Model RHH with Option

AG1, AG2, AG3, AG15, AG16, or D12C. (Does not apply to AG58 or D12G; see NOTE page 19.)

The input and/or the capacity of the heater changes with altitude.

TABLE 12 below lists inputs and capacities at altitudes

from sea level to 9,000 ft (2745M) in the United States and to 4,500 ft (1373M) in Canada for Model RDH.

TABLE 13,

page 22, lists the same information for Model RHH.

BTUH Inputs and Capacities by Altitude in the UNITED STATES for Model RDH

ALTITUDE

Normal

Input

Thermal

Output

Capacity

2-Stage

Minimum

Input

(applies to

AG2, AG3,

AG15,

AG16)

2-Stage with Venter

Motor Controller

Minimum Input

(applies to AG60,

AG61, AG62, DG1,

DG5, D12C)

Modulation

Minimum Input

(applies to Options

AG8, AG9, AG9H,

AG40, DG2, DG6,

D12B)

Normal

Input

Thermal

Output

Capacity

2-Stage

Minimum

Input

(applies to

AG2, AG3,

AG15,

AG16)

2-Stage with Venter

Motor Controller

Minimum Input

(applies to AG60,

AG61, AG62, DG1,

DG5, D12C)

Modulation

Minimum Input

(applies to Options

AG8, AG9, AG9H,

AG40, DG2, DG6,

D12B)

Normal

Input

Thermal

Output

Capacity

2-Stage

Minimum

Input

(applies to

AG2, AG3,

AG15,

AG16)

2-Stage with Venter

Motor Controller

Minimum Input

(applies to AG60,

AG61, AG62, DG1,

DG5, D12C)

Modulation

Minimum Input

(applies to Options

AG8, AG9, AG9H,

AG40, DG2, DG6,

D12B)

Natural

Propane Natural Propane

Natural

Propane Natural Propane

Natural Propane Natural Propane

Feet

Meters

RDH Size 75

RDH Size 100

RDH Size 125

0-2000

0-610

75,000

60,750

52,500

24,750

30,000

18,750

30,000 100,000 81,000

70,000

33,000

40,000

25,000

40,000 125,000 101,250

87,500

41,250

50,000

31,250

50,000

2001-3000

611-915

70,500

57,105

49,350

23,265

28,200

17,625

28,200

94,000

76,140

65,800

31,020

37,600

23,500

37,600

117,500

95,175

82,250

38,775

47,000

29,375

47,000

3001-4000 916-1220

69,000

55,890

48,300

22,770

27,600

17,250

27,600

92,000

74,520

64,400

30,360

36,800

23,000

36,800

115,000

93,150

80,500

37,950

46,000

28,750

46,000

4001-5000 1221-1525 67,500

54,675

47,250

22,275

27,000

16,875

27,000

90,000

72,900

63,000

29,700

36,000

22,500

36,000

112,500

91,125

78,750

37,125

45,000

28,125

45,000

5001-6000 1526-1830 66,000

53,460

46,200

21,780

26,400

16,500

26,400

88,000

71,280

61,600

29,040

35,200

22,000

35,200

110,000

89,100

77,000

36,300

44,000

27,500

44,000

6001-7000 1831-2135 64,500

52,245

45,150

21,285

25,800

16,125

25,800

86,000

69,660

60,200

28,380

34,400

21,500

34,400 107,500

87,075

75,250

35,475

43,000

26,875

43,000

7001-8000 2136-2440 63,000

51,030

44,100

20,790

25,200

15,750

25,200

84,000

68,040

58,800

27,720

33,600

21,000

33,600 105,000

85,050

73,500

34,650

42,000

26,250

42,000

8001-9000 2441-2745 61,500

49,815

43,050

20,295

24,600

15,375

24,600

82,000

66,420

57,400

27,060

32,800

20,500

32,800 102,500

83,025

71,750

33,825

41,000

25,625

41,000

Feet

Meters

RDH Size 150

RDH Size 175

RDH Size 200

0-2000

0-610

150,000 121,500

105,000

49,500

60,000

37,500

60,000 175,000 141,750

122,500

57,750

70,000

43,750

70,000 200,000 162,000

140,000

66,000

80,000

50,000

80,000

2001-3000

611-915

141,000 114,210

98,700

46,530

56,400

35,250

56,400 164,500 133,245

115,150

54,285

65,800

41,125

65,800 188,000 152,280

131,600

62,040

75,200

47,000

75,200

3001-4000 916-1220 138,000 111,780

96,600

45,540

55,200

34,500

55,200 161,000 130,410

112,700

53,130

64,400

40,250

64,400 184,000 149,040

128,800

60,720

73,600

46,000

73,600

4001-5000 1221-1525 135,000 109,350

94,500

44,550

54,000

33,750

54,000 157,500 127,575

110,250

51,975

63,000

39,375

63,000 180,000 145,800

126,000

59,400

72,000

45,000

72,000

5001-6000 1526-1830 132,000 106,920

92,400

43,560

52,800

33,000

52,800 154,000 124,740

107,800

50,820

61,600

38,500

61,600 176,000 142,560

123,200

58,080

70,400

44,000

70,400

6001-7000 1831-2135 129,000 104,490

90,300

42,570

51,600

32,250

51,600 150,500 121,905

105,350

49,665

60,200

37,625

60,200 172,000 139,320

120,400

56,760

68,800

43,000

68,800

7001-8000 2136-2440 126,000 102,060

88,200

41,580

50,400

31,500

50,400 147,000 119,070

102,900

48,510

58,800

36,750

58,800 168,000 136,080

117,600

55,440

67,200

42,000

67,200

8001-9000 2441-2745 123,000 99,630

86,100

40,590

49,200

30,750

49,200 143,500 116,235

100,450

47,355

57,400

35,875

57,400 164,000 132,840

114,800

54,120

65,600

41,000

65,600

Feet

Meters

RDH Size

225

RDH Size

250

RDH Size 300

0-2000

0-610

225,000 182,250

157,500

74,250

90,000

56,250

90,000 250,000 202,500

175,000

82,500

100,000

62,500 100,000 300,000 243,000

210,000

99,000

120,000 75,000 120,000

2001-3000

611-915

211,500 171,315

148,050

69,795

84,600

52,875

84,600 235,000 190,350

164,500

77,550

94,000

58,750

94,000 282,000 228,420

197,400

93,060

112,800 70,500 112,800

3001-4000 916-1220

207,000 167,670

144,900

68,310

82,800

51,750

82,800 230,000 186,300

161,000

75,900

92,000

57,500

92,000 276,000 223,560

193,200

91,080

110,400 69,000 110,400

4001-5000 1221-1525

202,500 164,025

141,750

66,825

81,000

50,625

81,000 225,000 182,250

157,500

74,250

90,000

56,250

90,000 270,000 218,700

189,000

89,100

108,000 67,500 108,000

5001-6000 1526-1830

198,000 160,380

138,600

65,340

79,200

49,500

79,200 220,000 178,200

154,000

72,600

88,000

55,000

88,000 264,000 213,840

184,800

87,120

105,600 66,000 105,600

6001-7000 1831-2135

193,500 156,735

135,450

63,855

77,400

48,375

77,400 215,000 174,150

150,500

70,950

86,000

53,750

86,000 258,000 208,980

180,600

85,140

103,200 64,500 103,200

7001-8000 2136-2440

189,000 153,090

132,300

62,370

75,600

47,250

75,600 210,000 170,100

147,000

69,300

84,000

52,500

84,000 252,000 204,120

176,400

83,160

100,800 63,000 100,800

8001-9000 2441-2745

184,500 149,445

129,150

60,885

73,800

46,125

73,800 205,000 166,050

143,500

67,650

82,000

51,250

82,000 246,000 199,260

172,200

81,180

98,400

61,500

98,400

Feet

Meters

RDH Size 350

RDH Size 400A

0-2000

0-610

350,000 283,500

245,000

115,500 140,000

87,500 140,000 400,000 324,000

280,000

132,000

160,000 100,000 160,000

2001-3000

611-915

329,000 266,490

230,300

108,570 131,600

82,250 131,600 376,000 304,560

263,200

124,080

150,400

94,000 150,400

3001-4000 916-1220 322,000 260,820

225,400

106,260 128,800

80,500 128,800 368,000 298,080

257,600

121,440

147,200

92,000 147,200

4001-5000 1221-1525 315,000 255,150

220,500

103,950 126,000

78,750 126,000 360,000 291,600

252,000

118,800

144,000

90,000 144,000

5001-6000 1526-1830 308,000 249,480

215,600

101,640 123,200

77,000 123,200 352,000 285,120

246,400

116,160

140,800

88,000 140,800

6001-7000 1831-2135 301,000 243,810

210,700

99,330

120,400

75,250 120,400 344,000 278,640

240,800

113,520

137,600

86,000 137,600

7001-8000 2136-2440 294,000 238,140

205,800

97,020

117,600

73,500 117,600 336,000 272,160

235,200

110,880

134,400

84,000 134,400

8001-9000 2441-2745 287,000 232,470

200,900

94,710

114,800

71,750 114,800 328,000 265,680

229,600

108,240

131,200

82,000 131,200

TABLE 12 - BTUH Inputs and Capacities by Altitude for Model RDH

5. With the heater operating, determine that the inlet (supply) pressure to the heater

for natural gas is between 5 inches w.c.

(or as noted on the rating plate) and 14

inches w.c. and for propane between 11 and 14 inches w.c. Take this reading as

close as possible to the heater. (Heaters are equipped with a gas valve that has an

inlet pressure tap.) If the inlet (supply) pressure is not within the specified range,

the inlet (supply) pressure must be corrected and Steps 3 and 4 repeated.

6. Find the High Altitude Adjustment label in the plastic bag that contained these

instructions. Using a permanent marker, fill-in the appropriate information from

TABLE 12A or 12B. Affix the label to a clean, dry, and conspicuous location on the

outside of the heater access panel.

BTUH Inputs and Capacities by Altitude in CANADA for Model RDH

ALTITUDE

Normal

Input

Thermal

Output

Capacity

2-Stage

Minimum

Input

(applies to

AG2, AG3,

AG15,

AG16)

2-Stage with Venter

Motor Controller

Minimum Input

(applies to AG60,

AG61, AG62, DG1,

DG5, D12C)

Modulation

Minimum Input

(applies to Options

AG8, AG9, AG9H,

AG40, DG2, DG6,

D12B)

Normal

Input

Thermal

Output

Capacity

2-Stage

Minimum

Input

(applies to

AG2, AG3,

AG15,

AG16)

2-Stage with Venter

Motor Controller

Minimum Input

(applies to AG60,

AG61, AG62, DG1,

DG5, D12C)

Modulation

Minimum Input

(applies to Options

AG8, AG9, AG9H,

AG40, DG2, DG6,

D12B)

Normal

Input

Thermal

Output

Capacity

2-Stage

Minimum

Input

(applies to

AG2, AG3,

AG15,

AG16)

2-Stage with Venter

Motor Controller

Minimum Input

(applies to AG60,

AG61, AG62, DG1,

DG5, D12C)

Modulation

Minimum Input

(applies to Options

AG8, AG9, AG9H,

AG40, DG2, DG6,

D12B)

Natural Propane Natural Propane

Natural Propane Natural Propane

Natural Propane Natural Propane

Feet

Meters

RDH Size

75

RDH Size

100

RDH Size

125

0-2000

0-610

75,000

60,750

52,500

24,750

30,000 18,750

30,000 100,000 81,000

70,000

33,000

40,000

25,000

40,000 125,000 101,250

87,500

41,250

50,000

31,250

50,000

2001-4500 611-1373 67,500

54,675

47,250

22,275

27,000 16,875

27,000

90,000

72,900

63,000

29,700

36,000

22,500

36,000 112,500 91,125

78,750

37,125

45,000

28,125

45,000

Feet

Meters

RDH Size

150

RDH Size

175

RDH Size

200

0-2000

0-610

150,000 121,500

105,000

49,500

60,000 37,500

60,000 175,000 141,750

122,500

57,750

70,000

43,750

70,000 200,000 162,000

140,000

66,000

80,000

50,000

80,000

2001-4500 611-1373 135,000 109,350

94,500

44,550

54,000 33,750

54,000 157,500 127,575

110,250

51,975

63,000

39,375

63,000 180,000 145,800

126,000

59,400

72,000

45,000

72,000

Feet

Meters

RDH Size

225

RDH Size

250

RDH Size

300

0-2000

0-610

225,000 182,250

157,500

74,250

90,000 56,250

90,000 250,000 202,500

175,000

82,500

100,000 62,500 100,000 300,000 243,000

210,000

99,000

120,000

75,000 120,000

2001-4500 611-1373 202,500 164,025

141,750

66,825

81,000 50,625

81,000 225,000 182,250

157,500

74,250

90,000

56,250

90,000 270,000 218,700

189,000

89,100

108,000

67,500 108,000

Feet

Meters

RDH Size

350

RDH Size

400A

0-2000

0-610

350,000 283,500

245,000

115,500 140,000 87,500 140,000 400,000 324,000

280,000

132,000 160,000 100,000 160,000

2001-4500 611-1373 315,000 255,150

220,500

103,950 126,000 78,750 126,000 360,000 291,600

252,000

118,800 144,000 90,000 144,000