beautypg.com

Reznor RXH (Outdoor PreevA) Unit Installation Manual User Manual

Page 49

background image

Form I-RDH/REH/RHH/RXH (12-14), P/N 215210 R14, Page 49

Compressor

Model

ARI

Tonnage

208/240 V 1 PH 208/240 V 3 PH 460 V3 PH 575 V3 PH

RLA

LRA

RLA

LRA

RLA LRA RLA LRA

ZP29K5

2.4

14.1

77.0

9.0

71.0

5.6

38.0

3.8

36.5

ZP57K3

4.8

30.1

158.0

20.5

155.0

9.6

75.0

7.6

54.0

TABLE 32 - Reheat Compressor

Compressor

- Reheat

circuit is

charged at

the factory

with R410A

Refrigerant

7.6.2 Reheat Module

(Options AU7L and

AU7R) Compressor -

RDH, REH, RHH, RXH

The compressor in the optional reheat module is a high efficiency hermetic scroll type

that is factory charged with R410A refrigerant. The compressor has a low pressure

cutoff (LPCO) switch for protection against damage due to a loss of charge. This pro-

tection prevents short cycling on the internal overload (IOL) which can pump the oil

out of the compressor. The compressor also has a manual reset high pressure cutout

(HPCO).

NOTE: See Operation/Maintenance Form O-PREEVA (in the Literature Bag), for

additional information on compressor maintenance and R410A refrigerant.

IMPORTANT: Do not release refrigerant to the atmosphere! If required service procedures

include the adding or removing of refrigerant, the service technician must comply with

all federal, state and local laws. The procedures discussed in this manual should only be

performed by a qualified HVAC technician.

DANGER

This reheat circuit contains R410A high pressure refrigerant. Hazards exist that could

result in personal injury or death. Installation, maintenance, and service should only be

performed by an HVAC technician qualified in R410A refrigerant and using proper tools and

equipment. DO NOT USE service equipment or tools designed for R22 refrigerant.

7.6.3 Remote Console

for Controls - RDH,

REH, RHH, RXH

If the system includes an optional control console, it is shipped separately for field

installation. A selection of remote consoles is available with a variety of combinations

of factory-mounted controls. All consoles include burner and blower indicator lights

and may include a dirty filter indicator light (see below); a cooling on indicator light;

an on/off switch; a summer/winter/off control switch; a heat/vent/cool system switch;

and/or a potentiometer for damper control. The thermostat or room command module

may also be mounted on the console. Depending on the console selected, it may be

10-3/4” (273mm) or 15-3/4” (400mm) in length. All consoles are 7-5/8” (194mm) high

and 2-5/8” (67mm) deep. Consoles may be flush or recess mounted. If recessing (not

using the mount ring) subtract 7/8” (22mm) from the height and width.
Wire the controls on the remote console according to the wiring diagram. Refer to

TABLE 28 on page 45 for minimum control wire gauge by length.
Dirty Filter Switch - If there is a dirty filter indicator light on the console, there is a dirty

filter switch in the unit. After the unit is started, before continuous operation, the dirty

filter switch must be set.

Modulating Reheat,

Option AUR1

With modulating reheat, a sensor monitors the air temperature as it leaves the reheat

coil. Based on a potentiometer setpoint and the sensor signal, the board will open or

close a refrigerant bypass valve. Changing the amount of refrigerant hot gas being

added to the refrigerant liquid before it enters the pre-cool coil will “modulate” the func-

tion of the pre-cool and reheat coils to provide the desired leaving air temperature.

FIGURE 43 - Dirty Filter Switch,

P/N 105507 (must be set prior to

continuous operation)

Set screw (on front of switch)

must be manually adjusted after

the system is in operation.

Negative pressure connection is

toward the “front or top” of the

switch (senses blower side of filters)

Positive pressure connection is

toward the “back or bottom” of the

switch (senses air inlet side of filters)

Instructions for Setting

Dirty Filter Switch

(FIGURE 43)

With clean filters in place; all doors closed (except electrical compartment); and the

blower opening, increase the pressure setting by adjusting the setscrew on the switch

clockwise until the filter light is energized or the screw is bottomed out. At that point,

adjust the setscrew three full turns counter clockwise or until the screw is top ended.

At that setpoint, the filter light will be activated at approximately 50% filter blockage.