beautypg.com

0 maintenance and service (cont'd), 2 maintenance procedures (cont'd) – Reznor RPBL Unit Installation Manual User Manual

Page 56

background image

Form I-SSCBL/RPBL, Page 56

.100

Top

View

Side

View

FIGURE 58 - Pilot

Assembly Spark Gap

10.0 Maintenance

and Service

(cont'd)

10.2 Maintenance

Procedures

(cont'd)

If no spark occurs, check the following:
a) Voltage between Terminals TH and 7 on the ignition controller should be at least

20 volts and no higher than 32 volts. Refer to Troubleshooting (Paragraph 10.3) if

no voltage is observed.

b) Short to ground in the high tension lead and/or ceramic insulator.
c) Pilot spark gap should be approximately .100".
NOTE: When checking for spark with the pilot burner assembly removed from the

burner rack, the pilot assembly must be grounded to the heater for proper spark.
If the above conditions are normal and no spark occurs, replace the ignition controller.

(See controller illustration and replacement information on page 51.)
If the main gas valve fails to open with a normal full size pilot flame established, check

for the following:
a) If voltage between black and brown leads on the main gas valve is 20 to 32

VAC and there is no main gas flow with the built-in manual valve in FULL OPEN

position, the main valve is defective.

b) If there is no voltage between black and brown leads on the main gas valve, check

for disconnected or shorted flame sensor lead or flame sensor probe.

When the above conditions are normal and the main gas flow is still off, the ignition

controller is probably defective. Do not attempt to service the ignition controller; it does

not contain any replaceable components.

10.2.3 Cleaning the Heat Exchanger

To clean the inner surfaces of the heat exchanger, remove the burner rack assembly

(See Paragraph 10.2.2.) permitting access to the inside of the heat exchanger tubes.
Clean the tubes using a 1/2" diameter furnace brush. A mirror and flashlight are helpful

in examining the narrow section of each tube. Remove any accumulated dust and soot.

10.2.4 Venter Motor

Power venter motors are permanently lubricated. No oiling is required.

10.2.5 Blower, Belt, and Drive

Check blower pulley and motor pulley to be sure they are secure to the shaft. Check

belt condition and belt tension (See Paragraph 6.5).
Blower Bearings - The blower bearings on models with less than a 10 HP motor

(standard blower) are permanently lubricated cartridge ball bearings and do not require

greasing.
The blower bearings on models equipped with a 10-20 HP motor are pillow block ball

bearings and are equipped with a grease fitting. These bearings should be lubricated

twice a year with a high temperature, moisture-resistant grease. (Type NLGI-1 or -2

standard grease is recommended.) Be sure to clean the grease fitting before adding

grease.
Add grease with a handgun until a slight bead of grease forms at the seal. Be careful

not to unseat the seal by over lubricating. NOTE: If unusual environmental conditions

exist (temperatures below 32°F or above 200°F; moisture; or contaminants), more

frequent lubrication is required.

CAUTION: If the blower is unused for more than three months,

bearings with a grease fitting should be purged with new grease

prior to startup.

10.2.6 Limit Control Check

With the heater on, completely block off the distribution air. The limit control should

open within a few minutes, shutting off gas supply to the main burners.

Pilot and Spark Ignition System (cont'd)

10.2.2 Pilot and Main Burners (cont'd)

This manual is related to the following products: