beautypg.com

3 unit inlet air, 0 mechanical (cont'd) – Reznor RPBL Unit Installation Manual User Manual

Page 26

background image

Form I-SSCBL/RPBL, Page 26

6.0 Mechanical

(cont'd)

6.3 Unit Inlet Air

6.2 Venting and Combustion Air (cont'd)

6.2.2 Venting Outdoor Power Vented Model RPBL (cont'd)

Vent Seal Plate,

P/N 43446

Oval Adapter Assembly,

P/N 103025

FIGURE 26A -

Installation

of Adapter

for Optional

Vertical Flue

Discharge

(Option CC3,

P/N 45021)

1) Remove and discard the louvered

discharge grill.

2) Using venter seal plate as a template, drill

holes. Use 3/8"-10 sheetmetal screws to

attach both the venter seal plate and the

oval adapter assembly.

5” Vent Cap,

P/N 110052

5” dia Flue Pipe

(1.2M)

5” dia

90° Elbow

18” (457mm) Straight Pipe

Oval Adapter Assy

Combustion Air Intake

Support angles for flue

pipe. Recommended

size is 1/2”x1/2”,

20 gauge

FIGURE 26B -

Installation of

the Vent Cap

(included in the

option package)

and the field-

supplied Piping

and Supports

Optional vertical vent piping provides compliance with local codes that require either

10-ft (3M) horizontal or 4-ft (1.2M) vertical clearance between the flue outlet and fresh

air intake of the heating system and/or the building.

6.3.1 100% Outside Air Hood - Model RPBL

Outside air hood (Option AS2) is a weatherized, screened hood designed to be field

assembled and installed around the horizontal inlet air opening of the blower cabinet.

The air hood includes a louver assembly designed to help eliminate moisture from the

inlet air. Complete installation instructions are packaged with the air hood option.

Optional

100%

Outside

Air Hood

43-17/32” (1106mm)

4-5/8”

(117mm)

31-11/32”

(796mm)

14” (356mm)

minimum

FIGURE 27 -

Dimensions of Outside

Air Hood, Option AS2

The width of the outside

air hood is the same as

the width of a blower

cabinet.

NOTE: Either a

manufacturer designed

optional air inlet hood as

shown in

FIGURE 27 or

an evaporative cooling

module as shown in

Paragraph 6.3.3 is required

to ensure complete weather

resistance.

Installation Instructions - 100% Outside Air Hood

Refer to

FIGURE 28. All screw ends except those across the bottom should be inside the air hood.

To avoid possible damage, it is recommended that the outside air hood be installed after the system has been placed

on the roof. The air hood should be installed before the heater is operated. Do not install the hood while the system

(furnace or blower) is in operation.
1. Top Panel -- On the air inlet side of the blower cabinet, remove the factory-installed screws attaching the blower

cabinet top. Slide the air hood top panel underneath the edge of the blower cabinet top.

The edge of the air

CAUTION: It is recommended that the inlet to the outside air hood NOT

be facing into the prevailing wind. Allow 14" minimum clearance from

the bottom of the air hood to the mounting surface.

This manual is related to the following products: