beautypg.com

Reznor RPBL Unit Installation Manual User Manual

Page 21

background image

Form I-SSCBL/RPBL, P/N 149159 R7, Page 21

16” (406mm)

minimum

24” (610mm)

maximum

Concentric

Adapter

Box

Wall

Screened

Exhaust

Cap

Inlet Air

Guard

Combustion Air to heater (seal joints)

Vent (Flue Exhaust) Pipe

from heater (seal joints)

Furnace

Distance between the

Concentric Adapter Box

and the Furnace Section.

For Maximum Length,

see Table on page 16.

Minimum length is 5 ft (1.5M).

Attach double-vent pipe to vent run no

more than 6” (152mm) from the box. A

taper-type reducer is required.

Attach box to wall with brackets.

One piece of

Double-Wall

Vent Pipe

2” (51mm)

(152

mm)

1” (25mm)

minimum

48”

(1219mm)

maximum

2” (51mm) if wall is combustible

Top View

6-15/16” (176mm)

Concentric Adapter Box

Double-Wall

Vent Pipe -

Pitch to

Drain

Thimble

Combustion Air Pipe - Pitch to Drain

3 ft (1M)

minimum

3 ft (1M)

minimum

6 ft (1.8M) minimum

Adjoining Building

Building Projection

Building Overhang

W a l l

Inlet Air

Guard

Exhaust (Vent) Cap

IMPORTANT: Install exhaust cap so the baffles

are positioned at 12:00, 3:00, 6:00, and 9:00 o’clock.

Side View

FIGURE 17 - Installation of a Typical Separated-Combustion Unit with Horizontal Vent and

Combustion Air Pipes (Option CC6)

Use a taper-type reducer to attach the 5" double-wall

vent pipe to the 6" or 7" single-wall or Category III vent

pipe run. Follow the instructions in

FIGURE 12, page 17.

8. Attach the exhaust (vent) cap to the end of the

vent pipe. Align the cap so that its baffle strips are

positioned on the horizontal and vertical centerlines (See

FIGURE 17). Follow the instructions in FIGURE 11, page

16, to attach the exhaust cap. (

NOTE: If vent pipe is

inserted from outside, cap may be attached before the

double-wall vent pipe is installed. If cap is attached first,

be sure the baffle strips are positioned correctly when

attaching the vent terminal pipe to the vent run.)
9. Seal the vent pipe. Verify that the double-wall section

of vent pipe has a slight downward drop (1/4” per foot /

6mm per 305mm) toward the vent terminal end. Use

10. Attach the indoor combustion air pipe. If using 6"

pipes, attach the single-wall combustion air pipe run to

the collar on the concentric adapter box with sheetmetal

screws. If using 7” pipe, install a taper type enlarger as

illustrated In

FIGURE 14, page 18.

Seal joints with tape or sealant.

Installation of the horizontal vent and combustion air sys-

tem on your separated-combustion unit is complete.

Ver-

ify compliance with all venting installation require-

ments, pages 15-18, and illustrated in FIGURE 17.

silicone sealant and seal the circumference of the pipe

and the opening of the box. Seal the area around the

pipe completely.

This manual is related to the following products: