beautypg.com

2 venting and combustion air – Reznor RPBL Unit Installation Manual User Manual

Page 15

background image

Form I-SSCBL/RPBL, P/N 149159 R7, Page 15

6.2 Venting and

Combustion Air

6.2.1 Separated-Combustion Model SSCBL

Each furnace section in the packaged system MUST BE equipped with both combus-

tion air and exhaust piping to the outdoors. Refer to

FIGURES 2 and 3 in Paragraph

4.1 for locations of vent and inlet air collars. The vent pipe collar is 6" O.D.; the inlet air

collar is 6" I.D. Either a horizontal (Option CC6) or vertical (Option CC2) combustion

air inlet/vent terminal concentric adapter assembly must be ordered for field installation

to each furnace section. Each concentric adapter assembly is shipped in a separate

carton. Be sure that the concentric adapter carton(s) are at the installation site.
These instructions apply to installation and use of the concentric adapter and vent/

combustion air kits (Option CC2 or CC6) designed for use with all Model SSCBL sys-

tems. The vent/combustion systems illustrated in this manual are the only vent/com-

bustion air systems approved for use with a Model SSCBL packaged heating system.

WARNING

Do not use an existing venting system. Installation of a combus-

tion air/vent system ordered as Option CC2 or Option CC6 is

required for each furnace section.

Installation should be done by a qualified agency in accordance with these instruc-

tions. The qualified service agency installing this separated-combustion system is

responsible for the installation.

WARNING

Model SSCBL separated combustion units are not designed or

approved for use in atmospheres containing flammable vapors

or atmospheres highly laden with chlorinated vapors. See Hazard

Levels, page 2.

6.2.1.1 Specific Venting

Requirements - Model

SSCBL

(read all venting

information before

installing)

1) Vent/Combustion Air Kit (ordered with the heater as either Option

CC2 or Option CC6)

All Model SSCBL installations

require a vent/combustion air kit for each furnace sec-

tion.

Follow the instructions on pages 19-21 to install a horizontal vent/combustion air sys-

tem (Option CC6). Follow the instructions on pages 22-25 to install a vertical vent/

combustion air system (Option CC2).

2) Type of Pipe (field-supplied)

Vent Pipe Between the Furnace Section and the Concentric Adapter Box - Use

either vent pipe approved for a Category III appliance OR single-wall, 26-gauge or

heavier galvanized (or a material of equivalent corrosion resistance) vent pipe.
Vent Pipe Between the Concentric Adapter Box and the Vent Cap - Double-wall

(Type B) vent pipe is required. The length of vent pipe that extends through the box

and runs concentric through the combustion air pipe must be one-piece with no joints.
Combustion Air Inlet Pipe - Sealed, single-wall galvanized pipe is recommended.

3) Venter Outlet and Combustion Air Inlet Collars

Each furnace section has both an inlet air and a venter outlet connection (See

FIGURE

2). Both are 6" diameter for all sizes.

NOTE: If using 7" pipe (see table

below), use a taper-type 6" to 7"

enlarger to attach the vent pipe

and a 7" to 6" reducer to attach

the combustion air pipe.

Taper-type

Enlarger

Airflow

Taper-type

Reducer

Airflow

4) Pipe Diameter and Length

Pipe diameters and maximum indoor vent lengths apply to both horizontal and vertical

vents. Add all straight sections and equivalent lengths for elbows. The total length of

the straight sections and elbows must not exceed the Maximum Length.

This manual is related to the following products: