beautypg.com

0 mechanical, 1 gas piping and pressures – Reznor RPBL Unit Installation Manual User Manual

Page 13

background image

Form I-SSCBL/RPBL, P/N 149159 R7, Page 13

6.0 Mechanical

6.1 Gas Piping and

Pressures

WARNING

This appliance is equipped for a maximum gas supply pressure of 1/2

psi, 3.5 kPa, or 14 inches water column. NOTE: Supply pressures higher

than 1/2 psi require installation of an additional service regulator exter-

nal to the unit.

Pressure Testing Supply Piping

Test Pressure Above 1/2 PSI: Disconnect the heater and manual valve from the gas

supply which is to be pressure tested. Cap or plug the supply line.
Test Pressure Below 1/2 PSI: Before testing, close the manual valve on the heater.

WARNING

Manifold gas pressure must never exceed 3.5" w.c. for natural gas or

10" w.c. for propane gas.

All piping must be in accordance with requirements outlined in the National Fuel Gas

Code ANSI/Z223.1 (latest edition) or CSA B149.1 and B149.2. (See Paragraph 1.4.)

Gas supply piping installation should conform with good practice and with local codes.
These separated-combustion units for natural gas are orificed for gas having a heating

value of 1000 (±50) BTU per cubic ft. If the gas at the installation does not meet this

specification, consult the factory for proper orificing.
Pipe joint compounds (pipe dope) shall be resistant to the action of liquefied petroleum

gas or any other chemical constituents of the gas being supplied.
Install a ground joint union and manual shutoff valve upstream of the unit control sys-

tem. The 1/8" plugged tapping in the shutoff valve provides connection for supply line

pressure test gauge. The National Fuel Gas Code requires the installation of a trap with

a minimum 3" drip leg. Local codes may require a longer drip leg, typically 6".
After all connections are made, disconnect the pilot supply at the control valve and

bleed the system of all air. Reconnect the pilot line and leak test all connections by

brushing on a soap or leak-detecting solution.

WARNING

All components of a gas supply system must be leak tested prior

to placing the equipment in service. NEVER TEST FOR LEAKS

WITH AN OPEN FLAME. See Hazard Levels, page 2.

Gas Connection Size

(Not Gas Supply Line Size)

SSCBL /

RPBL

400

500, 600, 700,

800, 1050, 1200

Natural Gas

1"

1-1/4"

Propane

1"

1-1/4"

Gas Connection

Gas Inlet

Curb

Cap

FIGURE 10 - Gas Connection and

Gas Train Manifold Arrangements

SSCBL or RPBL with 2 furnace sections

To furnace

Manual

shutoff

Adapter wth 1/8” NPT plugged

hole for pressure gauge connection

Gas Inlet

To furnace 1

Gas Inlet

Adapter wth

1/8” NPT plugged

hole for pressure

gauge connection

Manual

shutoff

To furnace 2

Manual

shutoff

To Furnace 1

Manual

Shutoff

Valve

Gas Inlet

To Furnace 2

Adapter with 1/8” NPT

plugged hole for pressure

gauge connection

To Furnace 3

Manual

Shutoff

Valve

SSCBL or RPBL with 3 furnace sections

SSCBL or RPBL with

1 furnace section

This manual is related to the following products: