beautypg.com

0 mechanical (cont'd), 2 venting and combustion air (cont'd), Cont'd) – Reznor RPBL Unit Installation Manual User Manual

Page 20

background image

Form I-SSCBL/RPBL, Page 20

FIGURE 16B - Brackets

for Attaching the

Concentric Adapter Box

to the Wall

1) Attach the Brackets to the Box - The 6”

(152mm) portion of each bracket is

designed with five 7/32” diameter holes

so that attachment to the box can be

adjusted.

If the wall is combustible, position brackets to

allow for a 2” (51mm) clearance between the

box and the wall.

Adjust bracket attachment to allow for the slight

downward pitch of the terminal vent pipe.

After careful positioning, use sheetmetal screws

to attach the brackets. NOTE: If any holes are

made in the box in error, they must be sealed.

2) Attach the Box to the Wall (Step 5)

When the box is attached to the wall in Step 5,

use the 2-1/2” (64mm) portion of the brackets.

To adjust to construction each bracket has

three 7/32” diameter holes.

C

C

26-1/8”

(664mm)

minimum

With more than one

furnace section, prepare

one hole per furnace

with spacing as shown.

FIGURE 16A - Prepare

holes so that there

is a minimum of 26-

1/8" (664mm) between

centerlines of each

terminal pipe.

b) Attach the outside portion of the combustion air pipe to the box. Determine

the length by measuring the bracket length from box to wall, plus the wall thickness,

plus 2" (51 mm). (The inlet air pipe should extend beyond the outside wall

approximately 2" (51mm).)
Attach the inlet air pipe to the collar of the concentric adapter with sheetmetal screws

and seal.
5. Attach the concentric adapter box to the wall. Insert the combustion air pipe

through the wall.

Attach the brackets (FIGURE 16B) to the wall. On the outside, caulk

or flash the inlet air pipe. Flashing is field-supplied.
6. Position the inlet guard over the end of the combustion air pipe. See FIGURE

17. Attach the guard to the inlet air pipe with the four 1/2" long screws.
7. Determine length and install the double-wall terminal vent pipe.

a) Determine length of pipe. The length of the vent pipe is determined by the

installation within the maximum and minimum requirements. See

FIGURE 17, to

determine lengths of each segment and calculate the total length required. The vent

pipe extending through the box and the inlet air pipe

must be one piece of double-

wall vent pipe without joints. The transition to the single-wall or Category III vent

pipe run, must be a maximum of 6” (152mm) from the heater side of the box.
b) Install double-wall terminal vent pipe. Being sure the vent pipe is in the proper

flow direction, slide the end through the box. Position the vent pipe so that it will

extend between 16" (406mm) and 24” (610mm) past the end of the combustion air

pipe and no more than 6” (152mm) out of the box toward the heater.

6.2 Venting and

Combustion Air

(cont'd)

6.0 Mechanical

(cont'd)

6.2.1.2 Horizontal Vent Instructions - Model SSCBL

(cont'd)

4. Prepare the Concentric Adapter Box

a) Attach the brackets to the box. Follow the instructions in FIGURE 16B.

3. Prepare a hole through the outside wall for the 8" (203mm) diameter

combustion air pipe. Outside wall construction thickness should be between 1"

(25mm) minimum and 48" (1143mm) maximum. The larger diameter combustion air

pipe serves as clearance for the vent pipe on non-combustible construction. A thimble

may be required depending on wall construction and/or local codes.
When installing a system with more than one furnace section, a minimum or 26-1/8"

(664mm) is required between the centerlines of each terminal pipe (

FIGURE 16A).

This manual is related to the following products: