Form I-SSCBL/RPBL, P/N 149159 R7, Page 23

FIGURE 20 - Brackets

for Attaching the

Concentric Adapter Box

to the Roof

5. Attach the concentric adapter box to the roof. On the inside, insert the

combustion air pipe up through the opening and attach brackets to the roof. (See

FIGURES 21 and 22.) On the outside, flash the combustion air pipe to the roof.

Flashing is field supplied

.

6. Determine the length and install the double-wall vent pipe.

a) Determine the length. See FIGURE 21 to determine the required length of the

vent pipe. The vent pipe extending through the box and the inlet air pipe

must be

one piece of double-wall vent pipe without joints.

FIGURE 21 - Assemble Concentric Adapter Box, Outdoor Combustion Air Pipe, and Double-Wall

Vent Pipe

Concentric Adapter Box

Mounting

Brackets

X = length of

combustion air pipe required

through and above the roof.

Height from box to top of inlet air

pipe must not exceed 48” (1219mm).

Minimum height above the roof is

18” (457mm) and must be higher

than anticipated snow depth.

First, attach Combustion Air Pipe and install the

Concentric Box
1)
Determine length (X) of pipe (see requirements on the left).
2) Attach the pipe to the collar on the box.
3) Attach the brackets to the roof.

V

ent Flow

22” (559mm) minimum

Cold Climate NOTE:

In geographic areas where

the design ambient is -10°F

or lower, this minimum

height is 34” (864mm).

Collar for

the Indoor

Portion

of the

Combustion

Air Pipe

Double-Wall Vent Pipe -

Extend length of double-wall

vent pipe a maximum of 6”

(152mm) below the box.

After box is installed, install Concentric Vent Pipe -

One piece of continuous double-wall pipe must extend

from a minimum of 3” (76mm) above the outer com-

bustion air pipe to a maximum of 6” (152mm) below
the box.
(NOTE: Vent pipe does not attach to the box;
it must be supported
.)
1) Calculate height (see requirements on the left).
2) Be sure vent flow marking on pipe is in the right direction.
3) Slide pipe through the box and the outer inlet air pipe.
4) Attach to vent run no more than 6” (152mm) from the
adapter box. See instructions on page 18.

Vent pipe

extending

through the

box and the

combustion

air pipe

MUST be one

continuous

piece of double-

wall vent pipe.

A second section

of double-wall pipe

is permitted, joining

the long continuous

piece of vent pipe a

minimum of 3” (76mm)

above the top of the

combustion air pipe.

3” (76mm)

minimum

1) Attach the Brackets to the Box - The 6” (152mm)

portion of each bracket is designed with five

7/32” diameter holes so that attachment to the

box can be adjusted.

If the roof is combustible, position brackets to allow for

a 2” (51mm) clearance between the box and the roof.

After careful positioning, use sheetmetal screws to

attach the brackets. NOTE: If any holes are made in

the box in error, they must be sealed.

2) Attach the Box to the Roof (Step 5)

When the box is attached to the roof in Step 5, use the

2-1/2” (64mm) portion of the brackets. To adjust to

construction each bracket has three 7/32” diameter holes.

Outside View with concentric adapter
box attached to underside of roof. Install
field-supplied flashing at roof opening.

Snow Clearance

18” (457mm) minimum

(NOTE: Maximum

from concentric adapter

box is 48” (1219mm)

FIGURE 22 - Slide attached

Combustion Air Pipe up

through the Roof