beautypg.com

Reznor RPBL Unit Installation Manual User Manual

Page 55

background image

Form I-SSCBL/RPBL, P/N 149159 R7, Page 55

10.2.2 Pilot and Main

Burners

Burner Rack Removal Instructions

Instructions apply to all furnace sections.

1. Turn off the gas supply.

2. Turn off the electric supply.

3. Remove control access side panel.

4. Disconnect the pilot tubing and flame sensor lead (spark pilot).

5. Mark and disconnect electric valve leads.

6. Uncouple the union in the gas supply.

7. Remove sheetmetal screws in the top corners of the burner rack assembly.

8. Pull "drawer-type" burner rack out of the furnace.
To disassemble the burner rack:

1. Remove Carryover System --

Natural Gas - Remove the flash carryover system from the "manifold end" of the

burner rack.

NOTE: Natural gas burner racks manufactured prior to Series 6 have

a lighter tube carryover system. Break the lighter tube connection at the orifice and

remove the supply tubing, the drip shield and the lighter tube.

Propane - Break the lighter tube connection at the regulator and remove the lighter

tube orifice supply tubing; remove the retaining screws in the drip shield and the

shield; remove the retaining screws and slide out the lighter tube.

2. Pull main burners horizontally away from injection opening and lift out.

3. Remove manifold bracket screws and remove manifold.

4. Change main burner orifices, if necessary.

5. Remove screws and lift out pilot burner.
Follow the instructions to clean. To re-assemble and replace, reverse the above proce-

dures being careful not to create any unsafe conditions.

CAUTION: When

cleaning, wearing

eye protection

is strongly

recommended.

equilibrium, close the manual shutoff valve. Observe the gas pressure. There

should be no loss of gas pressure on the manometer. If the manometer indicates

a loss of pressure, replace the combination gas valve before placing the heater in

operation.

NOTE: Operational pressure settings and instructions for checking pressure settings

are in Paragraph 6.2.

In the event the pilot flame is short and/or yellow, check the pilot orifice for blockage

caused by lint or dust accumulation. Remove the pilot orifice and clean with air pres-

sure. DO NOT REAM THE ORIFICE. Check and clean the aeration slot in the pilot

burner.

Clean the metal sensing probe and the pilot hood with an emery cloth and wipe off

the ceramic insulator. Check the spark gap; spark gap should be maintained to .100".

(Refer to

FIGURE 58.) After the pilot is cleaned, blow any dirt away with compressed

air.

Main burners may be cleaned using air pressure. Use an air nozzle to blow out scale

and dust accumulation from the burner ports. Alternately blow through the burner ports

and the venturi. Use a fine wire to dislodge any stubborn particles. Do not use anything

that might change the port size.

Clean the burner rack carryover systems with air pressure.

Cleaning Pilot and

Main Burners

Pilot and Spark Ignition

System

The ignition controller provides the high voltage spark to ignite the pilot service and also

acts as the flame safety device. After ignition of the pilot gas, the controller electroni-

cally senses the pilot flame. A separate solid metal probe in the pilot burner assembly

is used to sense the flame. A low voltage DC electrical signal is imposed on the metal

probe which is electrically insulated from ground.

Proper operation of the electronic

spark ignition system requires a minimum flame signal of .2 microamps DC as

measured by a microampmeter. When the pilot flame impinges on the sensing probe,

the flame acts as a conduction path to ground. This completes the DC circuit; the igni-

tion controller responds by energizing the main gas valve.

CAUTION: Due to high voltage on pilot spark wire and pilot electrode, do

not touch when energized. See Hazard Levels, 2.

This manual is related to the following products: