beautypg.com

0 mechanical (cont'd), 1 gas piping and pressures (cont'd), Sizing gas supply lines – Reznor RPBL Unit Installation Manual User Manual

Page 14

background image

Form I-SSCBL/RPBL, Page 14

Sizing Gas Supply Lines

Manifold or Orifice

(Valve Outlet) Pressure

Settings

6.0 Mechanical

(cont'd)

6.1 Gas Piping

and Pressures

(cont'd)

Capacity of Piping - Cubic Feet per Hour based on 0.3" w.c. Pressure Drop

Specific Gravity for Natural Gas -- 0.6 (Natural Gas -- 1000 BTU/Cubic Ft)

Specific Gravity for Propane Gas -- 1.6 (Propane Gas -- 2550 BTU/Cubic Ft)

Length

of Pipe

Diameter of Pipe

1"

1-1/4"

1-1/2"

2"

2-1/2"

Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane

20'

350

214

730

445

1100

671

2100

1281

3300

2013

30'

285

174

590

360

890

543

1650

1007

2700

1647

40'

245

149

500

305

760

464

1450

885

2300

1403

50'

215

131

440

268

670

409

1270

775

2000

1220

60'

195

119

400

244

610

372

1105

674

1850

1129

70'

180

110

370

226

560

342

1050

641

1700

1037

80'

170

104

350

214

530

323

990

604

1600

976

90'

160

98

320

195

490

299

930

567

1500

915

100'

150

92

305

186

460

281

870

531

1400

854

125'

130

79

275

168

410

250

780

476

1250

763

150'

120

73

250

153

380

232

710

433

1130

689

175'

110

67

225

137

350

214

650

397

1050

641

200'

100

61

210

128

320

195

610

372

980

598

Note: When sizing supply lines, consider possibilities of future expansion and increased requirements.

Refer to National Fuel Gas Code for additional information on line sizing.

Measuring manifold gas pressure cannot be done until the heater is in operation. It is

included in the steps of the "Check-Test-Start" procedure in Paragraph 9.0. The follow-

ing warnings and instructions apply.

For Natural Gas: When the heater leaves the factory, the combination valve is set so

that the outlet gas pressure of a single-stage valve or high fire of a two-stage valve is

regulated to 3.5" w.c. Low fire on a two-stage valve is set to 1.8" w.c. Inlet supply pres-

sure to the valve must be a minimum of 5" w.c. or

as noted on the rating plate and a

maximum of 14" w.c.

NOTE: Always check the rating plate for minimum gas sup-

ply pressure. Minimum supply pressure requirements vary based on size of burner

and the gas control option. Most units require a minimum of 5" w.c. of natural gas as

stated above, but larger sizes with electronic modulation require a minimum of 6" w.c.

natural gas supply pressure.
For Propane: When the heater leaves the factory, the combination valve is set so that

the outlet gas pressure of a single-stage valve or high fire of a two-stage valve is 10"

w.c. Low fire on a two-stage valve is set to 5" w.c. Inlet pressure to the valve must be

a minimum of 11" w.c. and a maximum of 14" w.c.

Before attempting to measure or adjust manifold gas pressure, the inlet (supply) pres-

sure must be within the specified range for the gas being used both when the heater is

in operation and on standby. Incorrect inlet pressure could cause excessive manifold

gas pressure immediately or at some future time.

Instructions to Check Valve Outlet (Manifold) Pressure:

1) With the manual valve (on the combination valve) positioned to prevent flow to the

main burners, connect a manometer to the 1/8" pipe outlet pressure tap in the valve.

NOTE: A manometer (fluid-filled gauge) is recommended rather than a spring type

gauge due to the difficulty of maintaining calibration of a spring type gauge.
2) Open the valve and operate the heater. Measure the gas pressure to the manifold.

To measure the low stage pressure on units equipped with a two-stage valve, discon-

nect the wire from the "HI" terminal on the valve. (Be sure to reconnect the wire.)

Normally adjustments should not be necessary to the factory preset regulator. If adjust-

ment is necessary, set pressure to correct settings by turning the regulator screw IN

(clockwise) to increase pressure. Turn regulator screw OUT (counterclockwise) to

decrease pressure. Consult the valve manufacturer's literature provided with the fur-

nace for more detailed information.

CAUTION: DO NOT bottom out the gas valve regulator adjusting

screw. This can result in unregulated manifold pressure causing

overfire and heat exchanger failure.

This manual is related to the following products: