beautypg.com

Reznor RPBL Unit Installation Manual User Manual

Page 17

background image

Form I-SSCBL/RPBL, P/N 149159 R7, Page 17

FIGURE 12 - Follow STEPS to join the Double-Wall (Type B) Pipe to the Taper-type Reducer that

Joins it to the Single-Wall or Category III Vent Run

Figure 12 - STEP 1

On the taper-type reducer, place a

continual 1/4” bead of silicone seal-

ant around the circumference.

Figure 12 - STEP 2

Insert the collar of the reducer into the

inner pipe of the double-wall pipe until

the bead of sealant contacts the inner

pipe creating a sealed joint.

Figure 12 - STEP 3

Spaced equally around the double-

wall pipe, drill three small holes

below the sealant ring. Insert 3/4 inch

long sheetmetal screws to secure the

joint. Do not overtighten screws.

Make this connection a maximum of 6" (152mm) from the concentric adapter box.

5" I.D.

Double-

Wall

Pipe

6" to 5"

or 7" to

5" Taper-

Type

Reducer

Do STEP

2 imme-

diately

following

STEP 1.

6) Support

Support horizontal runs every six feet (1.8M). Support vertical runs of type "B" double-wall or Category III vent pipe

in accordance with the requirements of the pipe manufacturer. Support single-wall vertical pipe in accordance with

accepted industry practices. Do not rely on the heater or the adapter box for support of either horizontal or vertical pipes.

Use non-combustible supports on vent pipe.

7) Clearance

Do not enclose the vent pipe or place pipe closer than 6" (152mm) to combustible material.

All separated combustion installations

require a concentric adapter box as illustrated in FIGURE 13. The concentric

adapter box is included in the vent/combustion air kit. Installation instructions depend on whether the vent system is

horizontal (Option CC6) or vertical (Option CC2).

8) Concentric Adapter Box

FIGURE 13 - A Concentric Adapter Box is Required for EACH Furnace Section of a Model SSCBL

Installation

View of Heater Connection Side

View of Vent Terminal Connection Side

P/N 205885, Concentric Adapter Box

Top View

Heater Side View

6” Collar for

Combustion

Air Pipe

Opening for

vent pipe to

pass through

the box

2” (51mm)

2” (51mm)

6-1/32”

(153mm)

8” dia Collar

for Combustion

Air Pipe

14-1/4”

(362mm)

(127mm)

5-7/32”

(133mm)

5-21/32”

(144mm)

diameter

5-9/32”

(134mm)

(102mm)

13-3/8” (340mm)

Collar for connecting indoor

portion of the combustion air pipe

Opening for double-wall vent

pipe to pass through the box.

End View

showing

Airflow

Gray Arrows

show Flow of

Combustion Air

Vent (exhaust gas) flows through

field-supplied double-wall pipe

that extends straight through

the concentric adapter box.

Collar for attaching outside

concentric portion of the 8"

combustion air pipe

Concentric

Adapter Box

Airflow

Dimensions

If cross supports are used under

the 4x4 rails, do not enclose the

area under the furnace; leave

open space for ventilation.

This manual is related to the following products: