beautypg.com

0 controls, 1 control locations, 2 fan control – Reznor RPBL Unit Installation Manual User Manual

Page 43

background image

Form I-SSCBL/RPBL, P/N 149159 R7, Page 43

Optional Downturn

Plenum Cabinet

(Option AQ5 or AQ8)

27 30 31 32 33 34 35 36 37 38 39 40

41 1 2 3

4 5 6

26 29 25 28 24 23 22 21 20 19 18 17 16 15 14 13 12

11B

11A

10 9 8

7

NOTE: Illustration

of cabinet is not

entirely accurate

for these models.

Models SSCBL and

RPBL have one,

two, or three furnace

sections.

FIGURE 46 -

Locations

of Standard

and Optional

Controls

8.0 Controls

8.1 Control Locations

1) Optional Auto Reset

Freezestat

2) Combustion Air Pressure

Switch

3) Optional Discharge Air

Firestat

4) Ignition Controller

5) Optional Maxitrol

Discharge Air Sensor

(Opt AG8 or AG9)

6) Optional Two-Stage

Controller (Opt AG3) or

Maxitrol Amplifier (Opt

AG7, AG8 or AG9)

7) Optional Main Low Gas

Pressure Switch

8) Optional Pilot High Gas

Pressure Switch

9) Optional Main High Gas

Pressure Switch

10) Time Delay Relay

(power-vented)

11A) Limit Control (disc type

limit control)

11B) Limit Control (capillary

type limit control)

12) Fan Control

13) Optional Freezestat Time

Delay Relay

14) Line Voltage Terminal

Block

15) Low Voltage Terminal

Block

16) Freezestat Relay

17) Optional Dirty Filter

Pressure Switch

18) Line Voltage Connection

(field)

19) Opt Convenience Outlet

and Outlet Transformer

20) Blower Motor Contactor or

Starter

21) Optional High Ambient

Limit Control and/or

Optional AG41 or 42 Heat

Stage Controls (2 or 4)

22) Optional Outside Air or

Return Air Controller

23) Optional Mixed Air

Controller

24) Optional Potentiometer

25) Optional Return Air

Dampers

26) Optional Two Position or

Modulating Damper Motor

27) Optional Outside Air

Damper

28) Optional Potentiometer

29) Optional Filters

30) Blower Motor

31) Optional Control Relays

(as required, 8 maximum)

32) Auto Reset Reverse Flow

Limit

33) Optional Return Air

Firestat

34) Low Voltage Terminal

Strip

35) Line Voltage Terminal

Strip

36) Control Transformer

37) Control Transformer (as

required)

38) Optional Damper Motor

Transformer

39) Low Voltage Connection

(field)

40) Optional Air Proving

Switch

41) Venter Assembly

8.2 Fan Control

1. A fan control provides for the following control of the blower.

(a) After the gas valve opens, there is a time delay of blower operation to prevent

the discharge of cold air.

(b) Blower operation continues after the thermostat is satisfied as determined by

the fan time delay.

2. To be sure that the blower can continue to operate, the power supply to the

furnace

MUST NOT be interrupted except when servicing the unit.

3. If the customer wants the furnace off at night, the gas valve circuit SHOULD

BE OPENED by a single pole switch wired in series with the thermostat. Some

thermostats are provided with this feature. Multiple units controlled from a single

thermostat are shut off in the same manner. For proper operation, be sure the fan

control wiring is observed

Refer to the wiring diagram furnished with the furnace. For location, See

FIGURE 46

Item 12.
Service NOTE: To replace a fan control on units manufactured prior to 11/04, a

replacement kit is required. Order

P/N 209184.

This manual is related to the following products: