beautypg.com

0 mechanical (cont'd), 2 venting and combustion air (cont'd) – Reznor RPBL Unit Installation Manual User Manual

Page 22

background image

Form I-SSCBL/RPBL, Page 22

FIGURE 18 - Parts

in the Vertical Vent

Terminal/Combustion

Air Package (Option

CC2) - One required for

each furnace section.

Components Required

- Factory and Field

6.2.1.3 Vertical Vent Instructions - Model SSCBL

Field-supplied

installation

requirements:

• Vent pipes - see requirements, page 15.

• Combustion air pipes - see requirements, page 15.

• Taper-type pipe diameter reducers and/or increasers as required

• Thimble (a thimble is not required if wall is of non-combustible construction)

• Flashing

• Sheetmetal screws, tape, and sealant as required

Exhaust

(Vent)

Terminal,

P/N 53326

Combustion

Air Inlet,

P/N 53330

Qty

P/N

Description

1

205896 Complete Vertical Vent Kit (Same as Option CC2)

1

205885 Concentric Adapter Box Assembly (See FIGURE 13, page 17.)

1

53326 Exhaust (Vent) Terminal (illustrated below)

1

53330 Combustion Air (illustrated below)

2

207232 Brackets for attaching Concentric Adapter Box (FIGURE 20, page 23)

1

53335 Tube of High Temperature Silicone Sealant

Installation Instructions for Vertical Vent/Combustion Air Kit Option CC2

1. Determine the Location of the Vent Terminal(s). - Select a location away

from fresh air intakes, allowing space for each concentric adapter box inside. Vent

terminals must be located from adjacent buildings as shown in

FIGURE 24, page 25.

A vent terminal is required for each furnace section. When more than one vertical

concentric vent/combustion air terminal (Option CC2) is being installed, the minimum

spacing between vent centerlines is determined by the minimum outdoor design

temperature (most extreme outdoor condition at the installation site).

2. Install the Vent Pipe and Combustion Air Pipe Run(s). - Use the type of

pipe specified (Requirement No. 2, page 15), and comply with the attachment

requirements in Requirement No. 3, page 15. Length must comply with Requirement

No. 4, pages 15-16.

Seal all joints. Due to the high temperature,

do not enclose the exhaust pipes or

place pipes closer than 6" (152 mm) to combustible material. Provide supports for the

pipes. Extend the runs to close to the roof at the location(s) selected in Step 1 above.

Minimum Outdoor Design

Temperature

Minimum Spacing between Centerlines

of Vent Pipes in Vertical Combustion Air/Vent Terminals

(Option CC2)

°F

°C

inches

mm

31 or warmer

0 or warmer

36

914

-10 to 30

-23 to -1

60

1524

less than -10 less than -23

84

2134

6.2 Venting and

Combustion Air

(cont'd)

6.0 Mechanical

(cont'd)

3. Prepare hole(s) through the roof for the 8" (203mm) diameter combustion air

pipe. - A thimble may or may not be required depending on building construction and/

or local codes. The larger diameter combustion air pipe serves as clearance for the

vent pipe on non-combustible construction.

4. Prepare the Concentric Adapter Box

a) Attach the brackets to the box. Follow the instructions in FIGURE 20.

b) Attach the outside portion of the combustion air pipe to the box. Determine

the length of the combustion air pipe so that dimension ”X” in

FIGURE 21 is equal to

the bracket length, plus the roof thickness, plus anticipated snow depth, but does not

exceed 48“ (1219mm) or have less than 18” (457mm) of pipe above the roof. Attach

the inlet air pipe to the collar of the concentric adapter box with sheetmetal screws.

6.2.1 Separated-Combustion Model SSCBL (cont'd)

WARNING

All vent terminals

must be positioned

or located away from

fresh air intakes,

doors and windows to

preclude combustion

products from

entering occupied

space. Failure to

comply could result

in severe personal

injury or death and/or

property damage.

This manual is related to the following products: